Files
zmVault/Untitled.md
T

921 B

  1. RETAIL TENANT ELECTRICAL SERVICE SHALL BE DERIVED FROM TENANT METERS IN THE MAIN ELECTRICAL ROOM. REFER TO ELECTRICAL DISTRIBUTION DIAGRAM ON SHEET E-401. ELECTRICAL CAPACITY IS BASED ON THE FOLLOWING PROVISIONS:
    1. SIX RETAIL TENANTS ANTICIPATED WITH THE FOLLOWING ELECTRICAL SERVICE. (2)200A, (3)400A, AND (1)6OOA AT 480V/3PH. PROVIDE THE FOLLOWING CONDUITS FOR EACH SPACE WHICH INCLUDES SPARE CONDUIT FOR ADDITIONAL 200A METER FOR FLEXIBILITY.
    2. EACH 200A SERVICE SHALL BE PROVIDED WITH (2) 2 1/2” EMPTY CONDUITS FROM MAIN ELECTRICAL ROOM TO RETAIL SPACE.
    3. EACH 400A SERVICE SHALL BE PROVIDED WITH (3) 2 1/2” EMPTY CONDUITS FROM MAIN ELECTRICAL ROOM TO RETAIL SPACE.
    4. EACH 600A SERVICE SHALL BE PROVIDED WITH (2) 3” AND (1) 2 1/2” EMPTY CONDUITS FROM MAIN ELECTRICAL ROOM TO RETAIL SPACE.
    5. GALLERY SERVICE SHALL BE PROVIDED WITH 200A WIRING AND CONDUIT.