2.9 KiB
id, aliases, title, tags, dg-publish
| id | aliases | title | tags | dg-publish | |||||
|---|---|---|---|---|---|---|---|---|---|
| electrical | Electrical Takeoff |
|
true |
Electrical Takeoff
Important
Complete pre-takeoff-research, including wiring-method-selection and wiring-device-research, before beginning takeoff.
Tip
Use heating-designations for uncertain scope.
Garage
In conventional slab garages, use ENT and PVC as permitted.
In precast slab garages, use EMT.
Receptacles
Floor Boxes
COMMON ASSEMBLIES/FLOOR BOXES/...
Poke-Thru's
Use suitable floor box assembly,
delete floor box items,
add ITEM DATABASE/WIRING & SYSTEM DEVICES/FLOOR BOXES & FITTTINGS/GENERIC - FLOOR BOXES & ACCESS/POKE-THRU W/ DUPLEX RECEPTACLE
Homeruns
Lighting Homeruns
Area= "XX - Level XX Building"Phase= "Building - Back of House (BOH)"
Takeoff homeruns in Building breakdowns, even where serving Amenity spaces.
Clubline Raceway
Clubline Raceway, also called CRG Raceway, is a glorified cable management trough.
Count receptacles normally, using surface-mount EMT assemblies.
Create a temporary item for the raceway itself.
Mechanical Connections
COMMON ASSEMBLIES/MECHANICAL CONNECTIONS .../...
When using length-based assemblies use adders per feeders-takeoff.
Stair Pressurization Fans
Assume branch circuit conductors must be protected per fire-resistive-wiring-methods-takeoff.
Roof Mounted Equipment
Unit Condensing Units
| Level | Horizontal | Vertical | Length | Count |
|---|---|---|---|---|
| Level 01 | 150 | 40 | 190 | |
| Level 02 | 150 | 30 | 180 | |
| Level 03 | 150 | 20 | 170 | |
| Level 04 | 150 | 10 | 160 |
Put homeruns on the Area of the dwelling unit.
Put connections on the Area of the CU.
.../CONDENSOR HOME RUNS
.../CU CONDENSER SLEEVE W/ FLEX - NO HMRN WIRE
NO SLEEVE:
Routed through a "doghouse"
(a large weatherproof opening)
with several other feeds.
Used where drilling openings for individual sleeves
would be impractical.
PVC SLEEVE, EMT SLEEVE:
Routed up through the roof,
(optionally through a disconnect)
with flex to the equipment.
Equipment Racks
Max 20 disconnects per rack
DISTRIBUTIION/TRAPEZE RACK SUPPORT .../...
Trash Chute
-
Horizontal:
COMMON ASSEMBLIES/MECHANICAL CONNECTIONS .../...- Length = Length per drawings, 100ft if not shown.
-
Vertical (Riser):
Area= "Typical - Building All Levels"
Takeoff:
COMMON ASSEMBLIES/MISC ASSEMBLIES/TRASH CHUTE RISER CIRCUIT...- Length = average floor to floor height
Fire/Smoke Dampers