Hello Team,
Below is a comprehensive list of means & methods for 1990 K Street. Please confirm you have received this email and respond with any questions or comments.
- Takeoff Request Stage: Full Takeoff %% Stage 1, Stage 1 + Units, Full takeoff %%
- Delivery Method: Plans & Specs %% Plans & Specs, Design Build, Design Assist, P&S with Approved VE %%
- Document Stage: Permit %% DD, CD, Permit, GMP, Bid, Awarded %%
- Drawings Date: 2025-12-05
- Project Manual Date: 2025-12-05
- Proposal Date: 2026-01-22
Project Specification Callouts
%% Put page of Drawing or PM after answer %%
-
Conduit:
- EMT Fittings: Set-screw ---Spec 260533.13 (p. 1423) %% GRC, coupling specs, etc. %%
-
Wire:
- Material: Aluminum 100A and larger ---E021 "ALUMINUM FEEDER SCHEDULE" Note 1(b)
- Acceptable Manufacturers: ---Spec 260519 (p. 1384)
- Alpha Wire; Brand of Belden, Inc.
- Belden Inc.
- Cerro Wire LLC
- Encore Wire Corporation
- General Cable; Prysmian Group North America
- Okonite Company
- Service Wire Co.
- Southwire Company, LLC
- WESCO
-
MC Cable:
- Application: Concealed feeders and branch circuits ---Spec 260519 (p. 1389) %% Branch homeruns only; Not permitted %%
- Acceptable Manufacturers: ---Spec 260519 (p. 1385-1386)
- AFC Cable Systems; Atkore International
- Alpha Wire; Brand of Belden, Inc.
- Belden Inc.
- Cerro Wire LLC
- Encore Wire Corporation
- General Cable; Prysmian Group North America
- Okonite Company
- Southwire Company, LLC
- WESCO
- ==Conductors: Copper ---Spec 260519 (p. 1386)==
- ==Armor: Steel ---Spec 260519 (p. 1386)==
- ==Jacket: PVC ---Spec 260519 (p. 1386)==
-
Steel Box Depth:
- Telecom: 2-1/8" ---Spec 270500 (p. 1673)
- Security: 2-1/8" ---Spec 280500 (p. 1753)
- Other Applications: Not specified %% 1-1/2", 2-1/8" %%
-
Floor Boxes: Sheet metal with brass or aluminum covers ---Spec 262719 (p. 1541)
-
Wiring Devices:
- Units:
- Current rating: Unspecified. Assuming 15A for takeoff.
- Standard/Decora: Unspecified. Assuming Toggle/Duplex for takeoff. %% 15A Decora %%
- BOH/Common Areas:
- Current rating: Unspecified. Assuming 20A for takeoff.
- Standard/Decora: Unspecified. Assuming Toggle/Duplex for takeoff. %% 20A Toggle/Duplex %%
- Units:
-
Switchboards:
- Acceptable Manufacturers: ---Spec 262413 (p. 1502)
- ABB, Electrification Business
- Eaton
- Siemens Industry, Inc., Energy Management Division
- Square D; Schneider Electric USA
- General Electric
- Bus Material: Aluminum ---Spec 262413 (p. 1503)
- Interrupting Current Rating: Not specified.
- Acceptable Manufacturers: ---Spec 262413 (p. 1502)
-
Distribution Panelboards:
- Acceptable Manufacturers: ---Spec 262413 (p. 1514-1515)
- Eaton
- Bus Material: Aluminum ---Spec 262413 (p. 1513)
- Breaker Types: Bolt-on ---Spec 262413 (p. 1515) %% Snap-on, bolt on %%
- Interrupting Current Rating: Not specified.
- Acceptable Manufacturers: ---Spec 262413 (p. 1514-1515)
-
Load Centers:
- Acceptable Manufacturers: ---Spec 262413 (p. 1514-1515)
- ABB, Electrification Business
- Eaton
- Siemens Industry, Inc., Energy Management Division
- Square D; Schneider Electric USA
- Bus Material: Aluminum ---Spec 262413 (p. 1513)
- Breaker Types: Plug-in ---Spec 262413 (p. 1515) %% Snap-on, bolt on %%
- Interrupting Current Rating: Not specified.
- ==Covers shall be factory-applied white paint.== ---Dwg. E401-E405 "ELECTRICAL DRAWING NOTES" (P)
- Acceptable Manufacturers: ---Spec 262413 (p. 1514-1515)
-
Transformers:
- Winding Material: Aluminum ---Spec 262213 (p. 1495)
- K-Rating: Not specified. %% Windings AL or CU, K-rating %%
-
Generator: (1) 600kW Diesel
- Enclosure Specs: Level 2 Sound Attenuating Weatherproof Enclosure ---Dwg. E014
- Remote Tank: None shown or specified.
- Tank Size: 24hrs at 100% load ---Spec 263213.13 (p. 1604)
- Load Banks: Internal, 50% load ---Dwg. E014, Spec 263213.13 (p. 1608)
- Acceptable Manufacturers: ---Spec 263213.13 (p. 1600)
- Caterpillar, Inc.; Electric Power Division
- Cummins Power Generation
- Generac
- Hipower Systems
- Kohler Power Systems
- Rolls-Royce Solutions America Inc
Project Drawing/Detail Callouts
Dwg. IDS-01A "OUTLET SPECIFICATIONS": Screwless Cover
Dwg. IDS-01A "SWITCHING SPECIFICATIONS": Legrand Tru-Universal Rocker/Dimmers (Is this for Amenity/Common Areas?)
PDI System Execution Plan
-
Primaries: Conduit and wiring excluded. ---Proposal 2026-01-22, Ex. B, Exclusions, Line 27 %% Installation only, (9) 6" PVC %%
-
Secondaries:
- Schedule 40 PVC UG; ---Proposal 2026-01-22, Ex. B, Inclusions Line 54-55
- wiring excluded. ---Proposal 2026-01-22, Ex. B, Exclusions, Line 28 %% PVC UG, GRC Stub-ups, AL %%
-
Feeders: PVC UG, EMT OH; AL 100A and larger; 2% voltage drop. %% PVC UG, EMT OH, AL over 100A, 2% VD %% %% Emergency Feeds MI Cable %%
-
Unit Subfeeds: MC OH; size per E025-E028 meter bank schedules; 3% voltage drop. %% MC OH AL, VD per Chart on E5.01 %%
-
Units:
- DW/Disposal - Separate Circuit
- Range - #6/3
- Kitchen Backsplash - Decora (Non-Combo Small Appliance Breakers)
- 120V Smokes
- EWH - #8/2
- VRF HVAC
- 20A Toggle Switches
- 15A Duplex Receptacles %% 15A Decora, Disposals, T-stat, Floor Boxes, Shade Control, Doorbells, Dimmer Switches, etc. %%
-
Telecom:
- 30" MSDE; ---T0.32/1 Note 3: "PRIMEX SOHOPRO P3000ND"
- (1) 1" innerduct to IDF. ---Proposal 2026-01-22, Ex. B, General Requirements, Line 114 %% 42" MSDE, No Cable Homeruns, (1) 1" Back to IDF, CAT6 with Stub-ups %%
-
EV Chargers: (2) dual circuit chargers with conduit, wire, data rough-in, and equipment. %% (42) Conduit only, (56) Conduit & Wire, (20) Conduit, Wire & Equipment %%
-
Fire Alarm: Devices PVC in-slab, Risers EMT. %% Free-air where allowed by code. EMT Risers. %%
-
DAS: System per PDI DAS Design. %% Conduit only, Per PDI DAS Design %%
-
Low Voltage: Free-air where allowed by code. %% Free-air where allowed by code. Stub-ups to accessible ceilings. %%
Lighting Control
-
Basis of Takeoff: Design per Plans and Specs ---Christian Pereiro 2026-02-11 %% Code Minimum per Energy Code Assigned, P&S, PDI Design %%
-
Area: ---Dwg. E021 "AUTOMATED LIGHTING CONTROL - SEQUENCES OF OPERATIONS"
- BOH: Line Voltage Control, no dimming
- Corridor: Digital Standalone Control, 0-10V dimming
- Amenity: Digital Standalone Control, 0-10V dimming
- Offices: Digital Standalone Control, 0-10V dimming, controlled receptacles as shown
- Site/Landscape: Line Voltage Control, no dimming
- Garage: Digital Standalone Control, 0-10V dimming %% Assign Method to Areas: Line Voltage, Low-Voltage Stand Alone or Centralized System %%
Takeoff will utilize assemblies including conduit rough-in, Cat5e cable, and device labor.
Tasks/Quotes Needed for WBS
%% Delete any completed %%
%% * Electrical Constructability Review %% %% * Electrical VDC %%
- Coordination Study %% * DAS Public Safety Raceway Design %%
Thank you,