%% Implementation of conest-pre-takeoff-email-template for 1990-k-street %%

Hello Team,

Below is a comprehensive list of means & methods for 1990 K Street. Please confirm you have received this email and respond with any questions or comments.

  • Takeoff Request Stage: Full Takeoff %% Stage 1, Stage 1 + Units, Full takeoff %%
  • Delivery Method: Plans & Specs %% Plans & Specs, Design Build, Design Assist, P&S with Approved VE %%
  • Document Stage: Permit %% DD, CD, Permit, GMP, Bid, Awarded %%
  • Drawings Date: 2025-12-05
  • Project Manual Date: 2025-12-05
  • Proposal Date: 2026-01-22

Project Specification Callouts

%% Put page of Drawing or PM after answer %%

  • Conduit:

    • EMT Fittings: Set-screw ---Spec 260533.13 (p. 1423) %% GRC, coupling specs, etc. %%
  • Wire:

    • Material: Aluminum 100A and larger ---E021 "ALUMINUM FEEDER SCHEDULE" Note 1(b)
    • Acceptable Manufacturers: ---Spec 260519 (p. 1384)
      • Alpha Wire; Brand of Belden, Inc.
      • Belden Inc.
      • Cerro Wire LLC
      • Encore Wire Corporation
      • General Cable; Prysmian Group North America
      • Okonite Company
      • Service Wire Co.
      • Southwire Company, LLC
      • WESCO
  • MC Cable:

    • Application: Concealed feeders and branch circuits ---Spec 260519 (p. 1389) %% Branch homeruns only; Not permitted %%
    • Acceptable Manufacturers: ---Spec 260519 (p. 1385-1386)
      • AFC Cable Systems; Atkore International
      • Alpha Wire; Brand of Belden, Inc.
      • Belden Inc.
      • Cerro Wire LLC
      • Encore Wire Corporation
      • General Cable; Prysmian Group North America
      • Okonite Company
      • Southwire Company, LLC
      • WESCO
    • ==Conductors: Copper ---Spec 260519 (p. 1386)==
    • ==Armor: Steel ---Spec 260519 (p. 1386)==
    • ==Jacket: PVC ---Spec 260519 (p. 1386)==
  • Steel Box Depth:

    • Telecom: 2-1/8" ---Spec 270500 (p. 1673)
    • Security: 2-1/8" ---Spec 280500 (p. 1753)
    • Other Applications: Not specified %% 1-1/2", 2-1/8" %%
  • Floor Boxes: Sheet metal with brass or aluminum covers ---Spec 262719 (p. 1541)

  • Wiring Devices:

    • Units:
      • Current rating: Unspecified. Assuming 15A for takeoff.
      • Standard/Decora: Unspecified. Assuming Toggle/Duplex for takeoff. %% 15A Decora %%
    • BOH/Common Areas:
      • Current rating: Unspecified. Assuming 20A for takeoff.
      • Standard/Decora: Unspecified. Assuming Toggle/Duplex for takeoff. %% 20A Toggle/Duplex %%
  • Switchboards:

    • Acceptable Manufacturers: ---Spec 262413 (p. 1502)
      • ABB, Electrification Business
      • Eaton
      • Siemens Industry, Inc., Energy Management Division
      • Square D; Schneider Electric USA
      • General Electric
    • Bus Material: Aluminum ---Spec 262413 (p. 1503)
    • Interrupting Current Rating: Not specified.
  • Distribution Panelboards:

    • Acceptable Manufacturers: ---Spec 262413 (p. 1514-1515)
      • Eaton
    • Bus Material: Aluminum ---Spec 262413 (p. 1513)
    • Breaker Types: Bolt-on ---Spec 262413 (p. 1515) %% Snap-on, bolt on %%
    • Interrupting Current Rating: Not specified.
  • Load Centers:

    • Acceptable Manufacturers: ---Spec 262413 (p. 1514-1515)
      • ABB, Electrification Business
      • Eaton
      • Siemens Industry, Inc., Energy Management Division
      • Square D; Schneider Electric USA
    • Bus Material: Aluminum ---Spec 262413 (p. 1513)
    • Breaker Types: Plug-in ---Spec 262413 (p. 1515) %% Snap-on, bolt on %%
    • Interrupting Current Rating: Not specified.
    • ==Covers shall be factory-applied white paint.== ---Dwg. E401-E405 "ELECTRICAL DRAWING NOTES" (P)
  • Transformers:

    • Winding Material: Aluminum ---Spec 262213 (p. 1495)
    • K-Rating: Not specified. %% Windings AL or CU, K-rating %%
  • Generator: (1) 600kW Diesel

    • Enclosure Specs: Level 2 Sound Attenuating Weatherproof Enclosure ---Dwg. E014
    • Remote Tank: None shown or specified.
    • Tank Size: 24hrs at 100% load ---Spec 263213.13 (p. 1604)
    • Load Banks: Internal, 50% load ---Dwg. E014, Spec 263213.13 (p. 1608)
    • Acceptable Manufacturers: ---Spec 263213.13 (p. 1600)
      • Caterpillar, Inc.; Electric Power Division
      • Cummins Power Generation
      • Generac
      • Hipower Systems
      • Kohler Power Systems
      • Rolls-Royce Solutions America Inc

Project Drawing/Detail Callouts

Dwg. IDS-01A "OUTLET SPECIFICATIONS": Screwless Cover

Dwg. IDS-01A "SWITCHING SPECIFICATIONS": Legrand Tru-Universal Rocker/Dimmers (Is this for Amenity/Common Areas?)

PDI System Execution Plan

  • Primaries: Conduit and wiring excluded. ---Proposal 2026-01-22, Ex. B, Exclusions, Line 27 %% Installation only, (9) 6" PVC %%

  • Secondaries:

    • Schedule 40 PVC UG; ---Proposal 2026-01-22, Ex. B, Inclusions Line 54-55
    • wiring excluded. ---Proposal 2026-01-22, Ex. B, Exclusions, Line 28 %% PVC UG, GRC Stub-ups, AL %%
  • Feeders: PVC UG, EMT OH; AL 100A and larger; 2% voltage drop. %% PVC UG, EMT OH, AL over 100A, 2% VD %% %% Emergency Feeds MI Cable %%

  • Unit Subfeeds: MC OH; size per E025-E028 meter bank schedules; 3% voltage drop. %% MC OH AL, VD per Chart on E5.01 %%

  • Units:

    • DW/Disposal - Separate Circuit
    • Range - #6/3
    • Kitchen Backsplash - Decora (Non-Combo Small Appliance Breakers)
    • 120V Smokes
    • EWH - #8/2
    • VRF HVAC
    • 20A Toggle Switches
    • 15A Duplex Receptacles %% 15A Decora, Disposals, T-stat, Floor Boxes, Shade Control, Doorbells, Dimmer Switches, etc. %%
  • Telecom:

    • 30" MSDE; ---T0.32/1 Note 3: "PRIMEX SOHOPRO P3000ND"
    • (1) 1" innerduct to IDF. ---Proposal 2026-01-22, Ex. B, General Requirements, Line 114 %% 42" MSDE, No Cable Homeruns, (1) 1" Back to IDF, CAT6 with Stub-ups %%
  • EV Chargers: (2) dual circuit chargers with conduit, wire, data rough-in, and equipment. %% (42) Conduit only, (56) Conduit & Wire, (20) Conduit, Wire & Equipment %%

  • Fire Alarm: Devices PVC in-slab, Risers EMT. %% Free-air where allowed by code. EMT Risers. %%

  • DAS: System per PDI DAS Design. %% Conduit only, Per PDI DAS Design %%

  • Low Voltage: Free-air where allowed by code. %% Free-air where allowed by code. Stub-ups to accessible ceilings. %%

Lighting Control

  • Basis of Takeoff: Design per Plans and Specs ---Christian Pereiro 2026-02-11 %% Code Minimum per Energy Code Assigned, P&S, PDI Design %%

  • Area: ---Dwg. E021 "AUTOMATED LIGHTING CONTROL - SEQUENCES OF OPERATIONS"

    • BOH: Line Voltage Control, no dimming
    • Corridor: Digital Standalone Control, 0-10V dimming
    • Amenity: Digital Standalone Control, 0-10V dimming
    • Offices: Digital Standalone Control, 0-10V dimming, controlled receptacles as shown
    • Site/Landscape: Line Voltage Control, no dimming
    • Garage: Digital Standalone Control, 0-10V dimming %% Assign Method to Areas: Line Voltage, Low-Voltage Stand Alone or Centralized System %%

Takeoff will utilize assemblies including conduit rough-in, Cat5e cable, and device labor.

Tasks/Quotes Needed for WBS

%% Delete any completed %%

%% * Electrical Constructability Review %% %% * Electrical VDC %%

  • Coordination Study %% * DAS Public Safety Raceway Design %%

Thank you,