vault backup: 2025-07-24 16:44:33
This commit is contained in:
@@ -0,0 +1,91 @@
|
||||
---
|
||||
id:
|
||||
aliases: []
|
||||
tags:
|
||||
- terminology
|
||||
---
|
||||
# Raceway Terms
|
||||
|
||||
## "Raceway"
|
||||
|
||||
> [!quote] NEC Article 100
|
||||
> **Raceway.**
|
||||
> An enclosed channel
|
||||
> designed expressly for holding wires, cables, or busbars,
|
||||
> with additional functions as permitted in this _Code_. (CMP-8)
|
||||
|
||||
### "Duct"
|
||||
|
||||
> [!quote] NEC 310.2 Definitions
|
||||
> **Electrical Ducts.**
|
||||
> Electrical conduits, or other raceways round in cross section,
|
||||
> that are suitable for use underground or embedded in concrete.
|
||||
|
||||
> [!info] Duct Bank
|
||||
> "Duct bank" is not given explicit definition in the NEC,
|
||||
> however it is used frequently to refer to any group of ducts,
|
||||
> _even as few as one_, as shown in Figure 310.60(C)(3).
|
||||
> It is always spelled as two words.
|
||||
|
||||
## "Wiring Method"
|
||||
|
||||
"Wiring method" is not given explicit definition in the NEC.
|
||||
|
||||
> [!quote] NEC 110.8 Wiring Methods
|
||||
> Only wiring methods recognized as suitable are included in this Code.
|
||||
> The recognized methods of wiring
|
||||
> shall be permitted to be installed in any type of building or occupancy,
|
||||
> except as otherwise provided in this Code.
|
||||
|
||||
> [!quote] NEC 300.1(A) All Wiring Installations
|
||||
> This article covers general requirements
|
||||
> for wiring methods and materials
|
||||
> for all _wiring installations_ (emphasis added)
|
||||
> unless modified by other articles in Chapter 3.
|
||||
|
||||
Nor is wiring installation, however by closest definition
|
||||
it can be assumed premises wiring includes all wiring installations.
|
||||
|
||||
> [!quote] NEC Article 100
|
||||
> **Premises Wiring (System).**
|
||||
> Interior and exterior wiring,
|
||||
> including power, lighting, control, and signal circuit wiring
|
||||
> together with all their associated hardware, fittings, and wiring devices,
|
||||
> both permanently and temporarily installed.
|
||||
> This includes
|
||||
> (a) wiring from the service point or power source to the outlets or
|
||||
> (b) wiring from and including the power source to the outlets where there is no service point.
|
||||
|
||||
Notably, Chapter 3 does not prescribe requirements for _raceway_, but for _wiring installations_.
|
||||
As such, conduit used for other purposes (e.g. routing beverage tubing) is out of scope.
|
||||
|
||||
Raceways used for supporting communications cables _would be_ out of scope,
|
||||
except for Article 800.110:
|
||||
|
||||
> [!quote] NEC 800.110(A)(1) Raceways Recognized in Chapter 3
|
||||
> Communications wires and cables shall be permitted
|
||||
> to be installed in any raceway included in Chapter 3.
|
||||
> The raceways shall be installed in accordance
|
||||
> with the requirements of Chapter 3.
|
||||
|
||||
Raceway is not a wiring method unless it is used to support premises wiring,
|
||||
which communications cabling is not.
|
||||
|
||||
It is not appropriate to say "EMT conduit is a wiring method"
|
||||
(granted the NEC does use this syntax occasionally),
|
||||
because a recognized wiring method must include
|
||||
the wiring, splices, pull boxes, outlet boxes, and supports
|
||||
necessary of a complete wiring installation,
|
||||
each of which has countless options.
|
||||
|
||||
It may be appropriate to refer to "MC cable" as a wiring method
|
||||
if you and your audience understand the name as shorthand
|
||||
for a more specific, standard framework.
|
||||
|
||||
## Takeaways
|
||||
|
||||
No part of a manufactured cable assembly (e.g. MC cable)
|
||||
can be considered a raceway.
|
||||
|
||||
It is usually incorrect to refer to wiring methods
|
||||
in the singular (e.g. installed in _a_ wiring method).
|
||||
Reference in New Issue