# Conduit Sizing
|
||||
|
||||
Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables
|
||||
|
||||
| Number of Conductors and/or Cables | Cross-Sectional Area (%) |
|
||||
| ---------------------------------- | ------------------------ |
|
||||
| 1 | 53 |
|
||||
| 2 | 31 |
|
||||
| Over 2 | 40 |
|
||||
|
||||
> [!info] Informational Note No. 1:
|
||||
> Table 1 is based on common conditions of proper cabling and alignment of conductors
|
||||
> where the length of the pull and the number of bends are within reasonable limits.
|
||||
> It should be recognized that, for certain conditions,
|
||||
> a larger size conduit or a lesser conduit fill should be considered.
|
||||
|
||||
> [!info] Informational Note No. 2:
|
||||
> When pulling three conductors or cables into a raceway,
|
||||
> if the ratio of the raceway (inside diameter)
|
||||
> to the conductor or cable (outside diameter)
|
||||
> is between 2.8 and 3.2, jamming can occur.
|
||||
> While jamming can occur when pulling four or more conductors or cables into a raceway,
|
||||
> the probability is very low.
|
||||
![[nfpa-70_ch09#Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables|Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables]]
|
||||
|
||||