@@ -26,6 +26,9 @@ Determine which Systems and Codes are required:
## PDI Lighting Control Configurations
> [!important]
> This section is currently not practical
### Stand Alone
0-10V dim -- "LV cable" is 2 conductor
@@ -42,19 +45,19 @@ Takeoff homeruns to the DLM (one per controlled circuit)
### Networked
#### Devices
"LV Cable" is [[twisted-pair-cable]]
##### Room Controllers
#### Room Controllers
No room controllers are necessary,
lighting zones are switched from a central lighting control panel (LCP)
##### Switches and Sensors
#### Switches and Sensors
Takeoff rough-in for switches and occupancy sensors
??
(only if time based; length based on closeness to sw/occ sensor)
(only if time based; length based on proximity to switch or occupancy sensor)
??
#### Homeruns
@@ -65,18 +68,26 @@ Takeoff 1 circuit homerun per lighting zone.
PDI default configuration
Takeoff (1) DLM controller for the fixtures
and (1) Plug controller for the receptacle
* If room has both dimmable fixtures and the controlled receptacle,
only (1) DLM controller and (1) Plug controller
* Use MC to cover room if drop
* Use EMT if exposed or MC not permitted
#### Room Controllers
For all rooms with dimmable fixtures
and/or automatically controlled receptacles,
take off (1) of either or both as appropriate.
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`DLM LTG RM CONTROLLER - ...`
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`REC PLUG CONTROLLER - ...`
Takeoff normal power to the controlled load
* Add LV cable to fixture branch
* Use 12/3 for receptacles
* Use \#12/3 for controlled receptacles
Takeoff rough-in for both the occ sensors and the LV switch
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`... LV SW - WALL ROUGH IN ...`
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`... SENSOR LOW VOLTAGE - ROUGH IN ...`
* Free air if possible
* **Length** = length of room
@@ -90,7 +101,14 @@ If occupancy sensors are shown in the corridors:
Takeoff homerun back to the electric room
Takeoff (1) DLM controller for each electric room
* Run free air down corridor
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`DLM LTG RM CONTROLLER - ...`
??
Run free-air down corridor
??
* **Length** = Length of corridor
Takeoff rough-in for each occupancy sensor shown.