1. RETAIL TENANT ELECTRICAL SERVICE SHALL BE DERIVED FROM TENANT METERS IN THE MAIN ELECTRICAL ROOM.
|
||||
REFER TO ELECTRICAL DISTRIBUTION DIAGRAM ON SHEET E-401.
|
||||
ELECTRICAL CAPACITY IS BASED ON THE FOLLOWING PROVISIONS:
|
||||
1. SIX RETAIL TENANTS ANTICIPATED WITH THE FOLLOWING ELECTRICAL SERVICE.
|
||||
(2)200A, (3)400A, AND (1)6OOA AT 480V/3PH.
|
||||
PROVIDE THE FOLLOWING CONDUITS FOR EACH SPACE
|
||||
WHICH INCLUDES SPARE CONDUIT FOR ADDITIONAL 200A METER FOR FLEXIBILITY.
|
||||
2. EACH 200A SERVICE SHALL BE PROVIDED WITH (2) 2 1/2” EMPTY CONDUITS FROM MAIN ELECTRICAL ROOM TO RETAIL SPACE.
|
||||
3. EACH 400A SERVICE SHALL BE PROVIDED WITH (3) 2 1/2” EMPTY CONDUITS FROM MAIN ELECTRICAL ROOM TO RETAIL SPACE.
|
||||
4. EACH 600A SERVICE SHALL BE PROVIDED WITH (2) 3” AND (1) 2 1/2” EMPTY CONDUITS FROM MAIN ELECTRICAL ROOM TO RETAIL SPACE.
|
||||
5. GALLERY SERVICE SHALL BE PROVIDED WITH 200A WIRING AND CONDUIT.
|
||||