@@ -714,7 +714,7 @@ Intermediate supports shall be provided
|
||||
as necessary to limit supported conductor lengths
|
||||
to not greater than those values specified in Table 300.19(A).
|
||||
|
||||
#### Table 300.19(A) Spacings for Conductor Supports
|
||||
#### Table 300.19(A) Spacings for Conductor Supports ^t300-19a
|
||||
|
||||
| Conductor Size | Aluminum or Copper-Clad Aluminum | Copper |
|
||||
| -------------------------------- | --------------------------------:| ------:|
|
||||
@@ -731,7 +731,7 @@ to not greater than those values specified in Table 300.19(A).
|
||||
Support methods and spacing intervals for fire-rated cables and conductors
|
||||
shall comply with any restrictions provided in the listing
|
||||
of the electrical circuit protective system used
|
||||
and in no case shall exceed the values in Table 300.19(A).
|
||||
and in no case shall exceed the values in [[#^t300-19a|Table 300.19(A)]].
|
||||
|
||||
#### 300.19(C) Support Methods.
|
||||
|
||||
@@ -752,7 +752,7 @@ One of the following methods of support shall be used:
|
||||
the cables being carried on two or more insulating supports
|
||||
and additionally secured thereto by tie wires, if desired.
|
||||
Where this method is used, cables shall be supported at intervals
|
||||
not greater than 20 percent of the support spacing in Table 300.19(A).
|
||||
not greater than 20 percent of the support spacing in [[#^t300-19a|Table 300.19(A)]].
|
||||
|
||||
4. Other approved means.
|
||||
|
||||
|
||||