@@ -45,7 +45,22 @@ Include [[sleeving-takeoff]] as necessary.
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FIRE PUMP ROOM ...`
### FACR to Elevator Shafts
### Elevator Control Rooms
> Also "Elevator Machine Room"
For each Elevator Control Room (ECR):
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...`
* **Count** = 1
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...`
* **Length** = Length measured from the most distant points of the FACR and ECR.
* Input adder length to reach the level of the ECR (Minimum 15ft).
### Elevator Shafts
`Area` = Same as FACR
@@ -73,19 +88,6 @@ For each elevator shaft:
> | 1 shaft | 2 shafts |
> ```
### FACR to Elevator Control Rooms
For each Elevator Control Room (ECR):
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...`
* **Count** = 1
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...`
* **Length** = Length measured from the most distant points of the FACR and ECR.
* Input adder length to reach the level of the ECR (Minimum 15ft).
### FACR to Stairwells
> [!info]
@@ -98,7 +100,7 @@ For each stairwell:
* **Length** = Length measured from the most distant points of the FACR and stairwell.
* Input adder length to reach the level of the stairwell (Minimum 15ft).
### Terminal Cabinets
## Terminal Cabinets
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`TERMINAL CABINET`/`ACE D ACCESSORY CABINET ENCLOSURE ...`
@@ -107,25 +109,33 @@ For each stairwell:
Horizontal:
`Area` = Same as FACR
* **Length** = Length measured from FACR to all electrical rooms
> * `Area` = Same as FACR
> * **Length** = Length measured from FACR to all electrical rooms
Vertical:
`Area` = "Typical - Building All Levels"
> * `Area` = "Typical - Building All Levels"
> * **Length** = 10ft
* **Length** = 10ft
### Annunciator Panels
## Annunciator Panels
> [!info] Also Known As
> * Fire Alarm Annunciator (FAA)
> * Fire Alarm Annunciator Panel (FAAP)
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`ANNUNCIATORS`/`REMOTE SERIAL ANNUNCIATOR ...`
> `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`ANNUNCIATORS`/`REMOTE SERIAL ANNUNCIATOR ...`
> * **Length** = Length measured from the FACR to FAA or Lobby
**Length** = Length measured from the FACR to FAA or Lobby
## Central Monitoring Loop
> [!important]
> Garden Style only.
> Fire Alarm Control Panels from each building will send a signal to a central location.
>
> In case of an emergency,
> the fire department will go to the central fire alarm station
> and find out what the issue is.
## Devices