vault backup: 2025-08-25 17:26:13

This commit is contained in:
2025-08-25 17:26:14 -04:00
parent 92c7eda666
commit b7b6657435
9 changed files with 4566 additions and 28 deletions
+32 -1
View File
@@ -45,7 +45,38 @@ tags:
3. Assign material to lengths and apply Voltage drop if applicable
4. Pigtails and Wireway Troughs if applicable
4. Pigtail Adaptors and Wireway Troughs if applicable
#### Pigtail Adaptors
![[burndy_AYP300.png]]
Pigtail adaptors are used where feeder wires exceed the range of panel lugs.
| Load Center Size | Max Feeder Size |
| ---------------- | --------------- |
| 100A | 2/0 AWG |
| 125A | 3/0 AWG |
| 225A | 300 kcmil |
| 400A | 500 kcmil |
`ITEM DATABASE`/`WIRE & CABLE ACCESSORIES`/`WIRE LUGS & SPLICING`/`PIGTAIL ADAPTORS...`/`ADAPTOR STRAIGHT PIGTAIL - ...`
> [!info]
> "Pigtail adaptor" is the most common name and spelling for the device,
> however it's something of a misnomer, having nothing to do with pigtails
> (a short length of wire),
> the name likely stemming from the device being used in lieu of a pigtail.
#### Meter Center Troughs
Only for PVC subfeeds where we own voltage drop.
- `Area` = "Typical - Building Levels With Meter Centers"
- `System` = "Electrical"
- `Phase` = "Sub Feeders"
`ITEM DATABASE`/`DISTRIBUTION`/`BUDGET ITEMS $ & LBR`/`METER CENTER WIRE TROUGH ($400/E)`
### 3. Extension (Review and Checking)