vault backup: 2025-10-24
This commit is contained in:
+42
-28
@@ -37,6 +37,12 @@ for a [[ibc-construction-types#5-Over-1 Construction|podium]] construction.
|
|||||||
> * Concealed: NM/SER
|
> * Concealed: NM/SER
|
||||||
> * Exposed to Structure: PVC OH
|
> * Exposed to Structure: PVC OH
|
||||||
|
|
||||||
|
<!--
|
||||||
|
This needs reworking.
|
||||||
|
I know PVC is preferable to MC in the case of feeders, subfeeds, and possibly home runs,
|
||||||
|
but I think they swap for branch.
|
||||||
|
-->
|
||||||
|
|
||||||
## Slab Thickness
|
## Slab Thickness
|
||||||
|
|
||||||
Conduits may not be routed through slabs of thickness
|
Conduits may not be routed through slabs of thickness
|
||||||
@@ -72,13 +78,32 @@ are not permissible in Non-Combustible (Type I, II) constructions.
|
|||||||
|
|
||||||
See [[ibc-construction-types]] for more info.
|
See [[ibc-construction-types]] for more info.
|
||||||
|
|
||||||
## By Wiring Method
|
## By Use-Case
|
||||||
|
|
||||||
|
### Multi-Circuit Homeruns
|
||||||
|
|
||||||
|
> [!quote] Art Baldwin (pp.)
|
||||||
|
> Multi-circuit MC is not cost-effective
|
||||||
|
> when considering the difficulty of rework.
|
||||||
|
> Use conduit, even EMT if necessary.
|
||||||
|
|
||||||
|
* Market Type = Assisted Living: MC-AP may be required.
|
||||||
|
|
||||||
|
## By Specification
|
||||||
|
|
||||||
|
> [!info] Example Specs Relevant to Wiring Methods Selection
|
||||||
|
> * 26XXXX - Raceway And Boxes For Electrical Systems
|
||||||
|
> * 26XXXX - Conduits For Electrical Systems
|
||||||
|
> * 26XXXX - Underground Ducts And Raceways For Electrical Systems
|
||||||
|
>
|
||||||
|
> * 26XXXX - Low-Voltage Electrical Power Conductors And Cables
|
||||||
|
>
|
||||||
|
> * 26XXXX - General Requirements For Electrical
|
||||||
|
> * 26XXXX - Common Work Results For Electrical
|
||||||
|
|
||||||
### Electrical Metallic Tubing (EMT)
|
### Electrical Metallic Tubing (EMT)
|
||||||
|
|
||||||
#### Fittings
|
Set-screw fittings may not be acceptable.
|
||||||
|
|
||||||
Set-screw < compression
|
|
||||||
|
|
||||||
> [!info]
|
> [!info]
|
||||||
> EMT has a third coupling type "indenter",
|
> EMT has a third coupling type "indenter",
|
||||||
@@ -105,29 +130,18 @@ May require rigid stub-ups in certain cases,
|
|||||||
which could make EMT more cost-effective.
|
which could make EMT more cost-effective.
|
||||||
Consult with the Senior Construction Estimator in this case.
|
Consult with the Senior Construction Estimator in this case.
|
||||||
|
|
||||||
## By Use-Case
|
## Flow Chart
|
||||||
|
|
||||||
### Multi-Circuit Homeruns
|
```mermaid
|
||||||
|
flowchart LR
|
||||||
|
A[Construction Type]
|
||||||
|
A -- I, II --> B[Can can be run in slab?]
|
||||||
|
B -- No --> D[Concealed?]
|
||||||
|
B -- Yes --> PVC
|
||||||
|
D -- No --> EMT
|
||||||
|
D -- Yes --> MC
|
||||||
|
A -- III, IV, V --> C[Concealed?]
|
||||||
|
C -- No --> PVC
|
||||||
|
C -- Yes --> NM/SER
|
||||||
|
|
||||||
> [!quote] Art Baldwin (pp.)
|
```
|
||||||
> Multi-circuit MC is not cost-effective
|
|
||||||
> when considering the difficulty of rework.
|
|
||||||
> Use conduit, even EMT if necessary.
|
|
||||||
|
|
||||||
## By Market Type
|
|
||||||
|
|
||||||
### Assisted Living
|
|
||||||
|
|
||||||
MC-AP may be required.
|
|
||||||
|
|
||||||
## Searching Specifications
|
|
||||||
|
|
||||||
> [!info] Example Specs Relevant to Wiring Methods Selection
|
|
||||||
> * 26XXXX - Raceway And Boxes For Electrical Systems
|
|
||||||
> * 26XXXX - Conduits For Electrical Systems
|
|
||||||
> * 26XXXX - Underground Ducts And Raceways For Electrical Systems
|
|
||||||
>
|
|
||||||
> * 26XXXX - Low-Voltage Electrical Power Conductors And Cables
|
|
||||||
>
|
|
||||||
> * 26XXXX - General Requirements For Electrical
|
|
||||||
> * 26XXXX - Common Work Results For Electrical
|
|
||||||
Reference in New Issue
Block a user