title: "NEC Article 110: Requirements for Electrical Installations"
|
||||
title: Article 110 Requirements for Electrical Installations
|
||||
---
|
||||
# NEC Article 110: Requirements for Electrical Installations
|
||||
# Article 110 Requirements for Electrical Installations
|
||||
|
||||
## Part I. General
|
||||
|
||||
@@ -171,9 +171,9 @@ Minimum Clear Distance
|
||||
|
||||
| Nominal Voltage to Ground | Condition 1 | Condition 2 | Condition 3 |
|
||||
| ------------------------- | ------------- | ------------------ | ------------- |
|
||||
| 0–150 | 900 mm (3 ft) | 900 mm (3 ft) | 900 mm (3 ft) |
|
||||
| 151–600 | 900 mm (3 ft) | 1.0 m (3 ft 6 in.) | 1.2 m (4 ft) |
|
||||
| 601–1000 | 900 mm (3 ft) | 1.2 m (4 ft) | 1.5 m (5 ft) |
|
||||
| 0--150 | 900 mm (3 ft) | 900 mm (3 ft) | 900 mm (3 ft) |
|
||||
| 151--600 | 900 mm (3 ft) | 1.0 m (3 ft 6 in.) | 1.2 m (4 ft) |
|
||||
| 601--1000 | 900 mm (3 ft) | 1.2 m (4 ft) | 1.5 m (5 ft) |
|
||||
|
||||