@@ -40,7 +40,7 @@ and shall comply with 110.14(C).
shall have an ampacity not less than the maximum load to be served
after the application of any adjustment or correction factors
in accordance with
[[nfpa-70_310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts 2000 Volts.|310.14]].
[[nfpa-70_310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts -- 2000 Volts.|310.14]].
Exception No. 1:
If the assembly, including the overcurrent devices protecting the feeder(s),