vault backup: 2025-11-10 16:55:49

This commit is contained in:
2025-11-10 16:55:49 -05:00
parent b904d4bd88
commit d677bff906
51 changed files with 1721 additions and 4040 deletions
+8 -8
View File
@@ -5,13 +5,13 @@ aliases:
tags:
- authorship/other
- destiny/uncertain
- exclude-from-word-count
- status/incomplete
- topic/construction/electrical
- type/media
- exclude-from-word-count
title: Article 310 Conductors for General Wiring
---
# Article 310: Conductors for General Wiring
# Article 310 Conductors for General Wiring
## Part I. General
@@ -64,7 +64,7 @@ or as permitted elsewhere in this Code.
<!-- TODO: TEXT OMITTED -->
### 310.14 Ampacities for Conductors Rated 0 Volts 2000 Volts.
### 310.14 Ampacities for Conductors Rated 0 Volts -- 2000 Volts.
#### 310.14(A) General.
@@ -202,11 +202,11 @@ shall be counted as a current-carrying conductor.
| Number of Conductors* | Percent of Values in Table 310.16 Through Table 310.19 as Adjusted for Ambient Temperature if Necessary |
| --------------------- | ------------------------------------------------------------------------------------------------------- |
| 46 | 80 |
| 79 | 70 |
| 1020 | 50 |
| 2130 | 45 |
| 3140 | 40 |
| 4--6 | 80 |
| 7--9 | 70 |
| 10--20 | 50 |
| 21--30 | 45 |
| 31--40 | 40 |
| 41 and above | 35 |
\*Number of conductors is the total number of conductors in the raceway or cable,