# Article 320 Armored Cable: Type AC
|
||||
|
||||
## Part I. General
|
||||
|
||||
### 320.1 Scope.
|
||||
|
||||
This article covers the use, installation, and construction specifications for armored cable, Type AC.
|
||||
|
||||
### 320.2 Definition.
|
||||
|
||||
The definition in this section shall apply within this article and throughout the Code.
|
||||
Armored Cable, Type AC.
|
||||
A fabricated assembly of insulated conductors in a flexible interlocked metallic armor. See 320.100.
|
||||
|
||||
### 320.6 Listing Requirements.
|
||||
|
||||
Type AC cable and associated fittings shall be listed.
|
||||
|
||||
## Part II. Installation
|
||||
|
||||
### 320.10 Uses Permitted.
|
||||
|
||||
Type AC cable shall be permitted as follows:
|
||||
|
||||
1. For feeders and branch circuits in both exposed and concealed installations
|
||||
2. In cable trays
|
||||
3. In dry locations
|
||||
4. Embedded in plaster finish on brick or other masonry, except in damp or wet locations
|
||||
5. To be run or fished in the air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampness
|
||||
|
||||
Informational Note: The "Uses Permitted" is not an all-inclusive list.
|
||||
|
||||
### 320.12 Uses Not Permitted.
|
||||
|
||||
Type AC cable shall not be used as follows:
|
||||
1. Where subject to physical damage
|
||||
2. In damp or wet locations
|
||||
3. In air voids of masonry block or tile walls where such walls are exposed or subject to excessive moisture or dampness
|
||||
4. Where exposed to corrosive conditions
|
||||
5. Embedded in plaster finish on brick or other masonry in damp or wet locations
|
||||
|
||||
### 320.15 Exposed Work.
|
||||
|
||||
Exposed runs of cable, except as provided in 300.11(B), shall closely follow the surface of the building finish or of running boards.
|
||||
Exposed runs shall also be permitted to be installed on the underside of joists where supported at each joist and located so as not to be
|
||||
subject to physical damage.
|
||||
|
||||
### 320.17 Through or Parallel to Framing Members.
|
||||
|
||||
Type AC cable shall be protected in accordance with 300.4(A), (C), and (D) where installed through or parallel to framing members.
|
||||
|
||||
### 320.23 In Accessible Attics.
|
||||
|
||||
Type AC cables in accessible attics or roof spaces shall be installed as specified in 320.23(A) and (B).
|
||||
|
||||
#### 320.23(A) Cables Run Across the Top of Floor Joists.
|
||||
|
||||
Where run across the top of floor joists, or within 2.1 m (7 ft) of the floor or floor joists across the face of rafters or studding, the cable
|
||||
shall be protected by guard strips that are at least as high as the cable. Where this space is not accessible by permanently instal led
|
||||
stairs or ladders, protection shall only be required within 1.8 m (6 ft) of the nearest edge of the scuttle hole or attic entrance.
|
||||
|
||||
#### 320.23(B) Cable Installed Parallel to Framing Members.
|
||||
|
||||
Where the cable is installed parallel to the sides of rafters, studs, or ceiling or floor joists, neither guard strips nor running boards shall
|
||||
be required, and the installation shall also comply with 300.4(D).
|
||||
|
||||
### 320.24 Bending Radius.
|
||||
|
||||
Bends in Type AC cable shall be made such that the cable is not damaged. The radius of the curve of the inner edge of any bend shall
|
||||
not be less than five times the diameter of the Type AC cable.
|
||||
|
||||
### 320.30 Securing and Supporting.
|
||||
|
||||
#### 320.30(A) General.
|
||||
|
||||
Type AC cable shall be supported and secured by staples; cable ties listed and identified for securement and support; straps, hangers,
|
||||
or similar fittings; or other approved means designed and installed so as not to damage the cable.
|
||||
|
||||
#### 320.30(B) Securing.
|
||||
|
||||
Unless otherwise permitted, Type AC cable shall be secured within 300 mm (12 in.) of every outlet box, junction box, cabinet, or fitting
|
||||
and at intervals not exceeding 1.4 m (41⁄ 2 ft).
|
||||
|
||||
#### 320.30(C) Supporting.
|
||||
|
||||
Unless otherwise permitted, Type AC cable shall be supported at intervals not exceeding 1.4 m (41⁄ 2 ft).
|
||||
Horizontal runs of Type AC cable installed in wooden or metal framing members or similar supporting means shall be considered
|
||||
supported and secured where such support does not exceed 1.4 m (41⁄ 2 ft) intervals.
|
||||
|
||||
#### 320.30(D) Unsupported Cables.
|
||||
|
||||
Type AC cable shall be permitted to be unsupported and unsecured where the cable complies with any of the following:
|
||||
1. Is fished between access points through concealed spaces in finished buildings or structures and supporting is impracticable
|
||||
2. Is not more than 600 mm (2 ft) in length at terminals where flexibility is necessary
|
||||
3. Is not more than 1.8 m (6 ft) in length from the last point of cable support to the point of connection to a luminaire(s) or other
|
||||
electrical equipment and the cable and point of connection are within an accessible ceiling
|
||||
For the purposes of this section, Type AC cable fittings shall be permitted as a means of cable support.
|
||||
|
||||
### 320.40 Boxes and Fittings.
|
||||
|
||||
At all points where the armor of AC cable terminates, a fitting shall be provided to protect wires from abrasion, unless the design of the
|
||||
outlet boxes or fittings is such as to afford equivalent protection, and, in addition, an insulating bushing or its equivalent protection shall
|
||||
be provided between the conductors and the armor. The connector or clamp by which the Type AC cable is fastened to boxes or
|
||||
cabinets shall be of such design that the insulating bushing or its equivalent will be visible for inspection. Where change is made from
|
||||
Type AC cable to other cable or raceway wiring methods, a box, fitting, or conduit body shall be installed at junction points as required
|
||||
in 300.15.
|
||||
|
||||
### 320.80 Ampacity.
|
||||
|
||||
The ampacity shall be determined in accordance with 310.14.
|
||||
|
||||
#### 320.80(A) Thermal Insulation.
|
||||
|
||||
Armored cable installed in thermal insulation shall have conductors rated at 90°C (194°F). The ampacity of cable installed in these
|
||||
applications shall not exceed that of a 60°C (140°F) rated conductor. The 90°C (194°F) rating shall be permitted to be used for
|
||||
ampacity adjustment and correction calculations; however, the ampacity shall not exceed that of a 60°C (140°F) rated conductor.
|
||||
Where more than two Type AC cables containing two or more current-carrying conductors in each cable are installed in contact with
|
||||
thermal insulation, caulk, or sealing foam without maintaining spacing between cables, the ampacity of each conductor shall be
|
||||
adjusted in accordance with Table 310.15(C)(1).
|
||||
|
||||
#### 320.80(B) Cable Tray.
|
||||
|
||||
The ampacity of Type AC cable installed in cable tray shall be determined in accordance with 392.80(A).
|
||||
|
||||
## Part III. Construction Specifications
|
||||
|
||||
### 320.100 Construction.
|
||||
|
||||
Type AC cable shall have an armor of flexible metal tape and shall have an internal bonding strip of copper or aluminum in intimate
|
||||
contact with the armor for its entire length.
|
||||
|
||||
### 320.104 Conductors.
|
||||
|
||||
Insulated conductors shall be of a type listed in Table 310.4(A) or those identified for use in this cable. In addition, the conductors shall
|
||||
have an overall moisture-resistant and fire-retardant fibrous covering. For Type ACT, a moisture-resistant fibrous covering shall be
|
||||
required only on the individual conductors.
|
||||
|
||||
### 320.108 Equipment Grounding Conductor.
|
||||
|
||||
Type AC cable shall provide an adequate path for fault current as required by 250.4(A)(5) or (B)(4) to act as an equipment grounding
|
||||
conductor.
|
||||
|
||||
### 320.120 Marking.
|
||||
|
||||
The cable shall be marked in accordance with 310.8, except that Type AC shall have ready identification of the manufacturer by
|
||||
distinctive external markings on the cable armor throughout its entire length.
|
||||