Fire Alarm Takeoff
Important
Complete conest-emergency-systems-research before beginning takeoff.
[!info] This note is intended for practice specific to pdi-estimating. See fire-alarm for information about fire alarm systems.
[!info] Breakdowns
System= "FA - Fire Alarm"
Assembly Selection
Free Air < PVC in Slab < EMT
- High Rise (Steel & slab): Free air in Units, use conduit elsewhere.1
- Mid Rise, High Density (Wood frame): Free air, conduit only where required.
Backbone
Include sleeving-takeoff as necessary.
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/...
Fire Command Center
-
Area= As shown.Phase= As shown.
.../
HEAD END EQUIP/... HEAD END
Generator Room
-
Area= Same as FACR.Phase= Same as FACR.
.../
GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/GENERATOR ROOM ...
Fire Pump Room
-
Area= Same as FACR.Phase= Same as FACR.
.../
GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FIRE PUMP ROOM ...
Elevator Control Rooms
Also "Elevator Machine Room (EMR)"
[!info] Breakdowns
Area= Same as FACR.Phase= Same as FACR.
For each Elevator Control Room (ECR):
-
.../
GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/ELEV CONTROL ROOM ...- Count = 1
-
.../
GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FACR TO ELEV CONTROL RM ...- Length = Length measured from the most distant points of the FACR and ECR.
- Input adder length to reach the level of the ECR (Minimum 15ft).
- Length = Length measured from the most distant points of the FACR and ECR.
Elevator Shafts
[!info] Breakdowns
Area= Same as FACR.Phase= Same as FACR.
For each elevator shaft:
-
.../
GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/ELEV SHAFT ...- Count = 1
-
.../
GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FACR TO ELEV SHAFT ...- Length = Length measured from the most distant points of the FACR and elevator shaft.
- Input adder length to reach the level of the shaft (Minimum 15ft).
- Length = Length measured from the most distant points of the FACR and elevator shaft.
[!important] Counting Elevator Shafts Adjacent elevators may be in the same or parallel shafts. Count the shafts accordingly:
+-----------------------------+--------------------------------+ | | | | || +--------+ +--------+ || | || +--------+ || +--------+ || | | || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || | | || +--------+ +--------+ || | || +--------+ || +--------+ || | | ||=======================|| | ||============||============|| | | 1 shaft | 2 shafts | +-----------------------------+--------------------------------+
FACR to Stairwells
[!info] This is for the Flow/Tamper modules in the stairwells
For each stairwell:
-
Area= Same as FACR.Phase= Same as FACR.
.../
GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FACR TO STAIRWELLS 1" CONDUIT ...- Length = Length measured from the most distant points of the FACR and stairwell.
- Input adder length to reach the level of the stairwell (Minimum 15ft).
Terminal Cabinets
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/TERMINAL CABINET/ACE D ACCESSORY CABINET ENCLOSURE ...
- Garden Style, High Density: (2) 1"C
- High Rise: (2) 2"C
-
Horizontal:
Area= Same as FACR.
... HORIZONTAL RUN- Length = Length measured from FACR to all electrical rooms
-
Vertical:
Area= "Typical - Building All Levels"
... RISER- Length = 10ft
Important
Annunciator Panels
[!info] Also Known As
- Fire Alarm Annunciator (FAA)
- Fire Alarm Annunciator Panel (FAAP)
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/ANNUNCIATORS/REMOTE SERIAL ANNUNCIATOR ...- Length = Length measured from the FACR to FAA or Lobby
Central Monitoring Loop
[!info] Breakdowns
System= "FAR - Fire Alarm Loop"
Important
Garden Style only.
Fire Alarm Control Panels from each building will send a signal to a central location.
In case of an emergency, the fire department will go to the central fire alarm station and find out what the issue is.
Devices
Takeoff should always(?) use the
DOES NOT INCLUDE COST OF DEVICES AND CABLE assemblies,
since we will always(?) have a fire alarm quote.
Smoke Detectors
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INITIATING DEVICES WITH WIRE - .../SMOKE DETECTOR W/ BASE - ...- Count: As shown, otherwise (1) every stairwell at every level.
Pull Stations
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INITIATING DEVICES WITH WIRE - .../PULL STATION - ...- Count: As shown, otherwise (1) every stairwell at every level and every exterior exit.
Flow/Tamper Switches
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INITIATING DEVICES .../ADDRESSABLE DUAL MONITOR MODULE - FLOW/TAMPER - ...(No free-air)- Count: As shown, otherwise (1) every stairwell at every level.
Magnetic Door Holders
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INDICATING DEVICES WITH WIRE - .../MAGNETIC DOOR HOLDER - ...- Count: As shown, otherwise (2) every set of double doors. (Typical of elevator lobbies and corridors)
Horns, Speakers, and Strobes
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INDICATING DEVICES WITH WIRE - .../INDOOR HORN STROBE - ...
Design Build (method 1):
- Count every 75 ft,
- measure with circles on Bluebeam
- or divide relevant SF area by 44152
- every elevator lobby, and
- every BOH room on the first floor and garage levels.
Design Build (alternative method):
- 15ft from end of corridor,
- then every 50ft
Fire/Smoke Dampers (FSD's)
[!info] Refers to fire, smoke, and combination fire/smoke dampers.
In pdi-building-types#High Rise, usually found on every level with units.
Tip
If possible, use
Area= "Typical - Fire Smoke Dampers" with quantity per level as shown.
For each damper, take off both
-
System= "FA - Fire Alarm"
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INITIATING DEVICES .../ADDRESSABLE OUTPUT RELAY CONTROL MODULE ... -
System= "EL - Electrical"
COMMON ASSEMBLIES/MISC ASSEMBLIES/FSD ...
-
\pi(\frac{75}{2})^2 \approx 4415↩︎