## Wire Properties
|
|
|
|
### Resistance
|
|
|
|
NEC Chapter 9 Tables [[nfpa-70_ch09#Table 8 Conductor Properties|8]]
|
|
and [[nfpa-70_ch09#Table 9 Alternating-Current Resistance and Reactance for 600-Volt Cables, 3-Phase, 60 Hz, 75°C (167°F) — Three Single Conductors in Conduit|9]]
|
|
provide resistance values for sizes and materials of wires,
|
|
stated in their notes to be based on calculations
|
|
found in [[nbs_1966_handbook-100]]
|
|
and [[nbs_1972_handbook-109]].
|
|
|
|
#### International Annealed Copper Standard
|
|
|
|
The same tables give conductor conductivity as a percent of
|
|
[International Annealed Copper Standard (IACS)](https://en.wikipedia.org/wiki/International_Annealed_Copper_Standard),
|
|
viz. 100% for copper and 61% for aluminum.
|
|
|
|
The definition of the IACS,
|
|
as originally published in [[nbs_1914_circular-031]] is
|
|
|
|
$$
|
|
100\%\ \rm{IACS} \equiv 0.15328~\text{ohm (meter, gram) at 20°C},
|
|
$$
|
|
|
|
alternately denoted in [[nbs_1966_handbook-100]] as
|
|
|
|
$$
|
|
0.15328~\text{ohm-gram/meter$^2$ at 20°C}.
|
|
$$
|
|
|
|
These definitions are for **mass resistivity**.
|
|
|
|
**Volume resistivity** can be derived
|
|
using the density of copper at the same temperature,
|
|
|
|
$$
|
|
8.89~\text{gram/cm$^3$ at 20°C},
|
|
$$
|
|
|
|
or
|
|
|
|
$$
|
|
0.32117~\text{lb/in.$^3$ at 20°C}.
|
|
$$
|
|
|
|
The derived value of volume resistivity given by [[nbs_1966_handbook-100]] is
|
|
|
|
$$
|
|
0.017241~\text{ohm-mm$^2$/meter at 20°C}.
|
|
$$
|
|
|
|
equal to 58 S/mm at 20°C.
|