51 lines
1.9 KiB
Markdown
51 lines
1.9 KiB
Markdown
---
|
|
id:
|
|
aliases: []
|
|
title: Medium Voltage
|
|
tags:
|
|
- topic/construction/electrical
|
|
- type/encyclopedia-entry
|
|
up: "[[electrical]]"
|
|
dg-publish: true
|
|
---
|
|
# Medium Voltage
|
|
|
|
"Medium voltage" refers to voltage systems greater than 600V.
|
|
|
|
## Insulation Level
|
|
|
|
> [!example]
|
|
>
|
|
> > [!cite] 343 Madison Avenue Project Specifications, emphasis added
|
|
> > 2.2 MEDIUM VOLTAGE CABLES (CON EDISON)
|
|
> > * ...
|
|
> > * H. Construction
|
|
> > * ...
|
|
> > * 3. Insulation
|
|
> > * ...
|
|
> > * c. _The minimum average insulation thickness shall be not less than 175 mils._
|
|
> > The minimum thickness at any cross-section of the insulation
|
|
> > shall be not less than 90% of the specified minimum average thickness.
|
|
>
|
|
> In this case 100% insulation level is appropriate for 15kV conductors.
|
|
|
|
[[nfpa-70_311_mv-conductors#311.10(B) Thickness of Insulation and Jacket for Nonshielded Insulated Conductors.]]
|
|
|
|
| Voltage Rating | Insulation Level | Insulation Thickness |
|
|
| --------------:| ----------------:| --------------------:|
|
|
| 5kV | 100% | 90 mils |
|
|
| 5kV | 133% | 115 mils |
|
|
| 5kV | 173% | 140 mils |
|
|
| 8kV | 100% | 115 mils |
|
|
| 8kV | 133% | 140 mils |
|
|
| 8kV | 173% | 175 mils |
|
|
| 15kV | 100% | 175 mils |
|
|
| 15kV | 133% | 220 mils |
|
|
| 15kV | 173% | 260 mils |
|
|
| 25kV | 100% | 260 mils |
|
|
| 25kV | 133% | 320 mils |
|
|
| 25kV | 173% | 420 mils |
|
|
| 35kV | 100% | 345 mils |
|
|
| 35kV | 133% | 420 mils |
|
|
| 35kV | 173% | 580 mils |
|