# Voltage Drop
> [!info] Ohm's Law
>
> $$
> V = I \times R, \quad R = \frac{V}{I}, \quad I = \frac{V}{R}
> $$
## Step 1: Effective Impedance $Z$
The formula for effective impedance $Z$ is given by
$$
Z = R \cos(\theta) + X \sin(\theta)
$$
where
* $R$ = AC resistance
* $X$ = Reactance
* $\theta$ = Power factor angle = $\arccos(\text{PF})$
### Parallel Runs
The equivalent resistance of parallel resistances is given by
$$
\frac{1}{R_{\text{eq}}} = \frac{1}{R_1} + \frac{1}{R_2} + \frac{1}{R_3} + \dots + \frac{1}{R_n}
$$
For $n$ parallel resistances of value $R$
$$
\begin{align*}
\frac{1}{R_{\text{eq}}} &= n \times \left(\frac{1}{R}\right) \\
&= \frac{n}{R} \\
R_{\text{eq}} &= \frac{R}{n}
\end{align*}
$$
## Step 2: Voltage Drop
> [!important]
> This section assumes a 3-phase
> 208Y/120V or 480Y/277V voltage system
> [!info] 3-Phase Voltage
>
> $$
> V_{L} = \sqrt{3} \times V_{P}, \quad V_{P} = \frac{V_{L}}{\sqrt{3}}
> $$
3% allowable voltage drop for a 120V line-to-neutral load:
$$
\text{Max}\ \Delta V = 0.03 \times 120 \text{V}_{P} = 3.60 \text{V}_{P}
$$
3% allowable voltage drop for a 208V line-to-line load:
$$
\text{Max}\ \Delta V = 0.03 \times 208 \text{V}_{L} = 6.24 \text{V}_{L}
$$
### Line to Neutral Loads
$$
\Delta V_{P} = I \times Z \times 2L
$$
### Line to Line Loads
$$
\Delta V_{L} = I \times Z \times 2L
$$
### 3-Phase Loads
$$
\Delta V_{3\phi} = \sqrt{3} ( I \times Z \times L )
$$
where
* $\Delta V$ = Voltage drop in volts ($V$)
* $I$ = Current in amperes ($A$)
* $L$ = Length of wire one way in feet ($\text{ft}$)
> [!important]
> "Current" is not the OCPD rating,
> but the actual load.
***
It is often more useful to know the maximum length
a certain wiring configuration is suitable for.
$$
L = \frac{ \Delta V }{ I \times M } \times \frac{1}{Z}
$$