tags:
|
|
- occupational/takeoff
|
|
- status/draft
|
|
- type/guide
|
|
title: Fixture Designations
|
|
---
|
|
# Fixture Designations
|
|
|
|
This note details creation of fixture designations
|
|
for use in [[fixtures-takeoff]].
|
|
|
|
## Name Format
|
|
|
|
There is no standard convention
|
|
for fixture designation names
|
|
in the [[conest-body-of-knowledge]].
|
|
The best any estimator can do
|
|
is be internally consistent.
|
|
|
|
My own preference is similar to
|
|
|
|
`A - Surface (Pendant) = 2.0hrs - #12 MC+LV 20ft`,
|
|
|
|
described by the pseudo-[[regular-expression|regex]] below:
|
|
|
|
```regex
|
|
<phase-abbr> - <assembly>(: <assembly-subtype>)?( \(<comment>\))?( = <fixture-labor>)? <wiring-method> <branch-length>ft
|
|
```
|
|
|
|
### Phase Abbreviation (`<phase-abbr>`)
|
|
|
|
|
|
|
|
### Assembly (`<assembly>`)
|
|
|
|
[[luminaire-types]]
|
|
|
|
* "Surface" - Assembly includes a junction box
|
|
* "Recessed" - Assembly does not include a junction box
|
|
|
|
### Assembly Subtype (`<assembly-subtype>`)
|
|
|
|
### Comment (`<comment>`)
|
|
|
|
In contrast to Assembly Subtype,
|
|
Comment reflects a distinction between fixture types or use case
|
|
_which does not affect the contents of the designation._
|
|
That is, `Surface`, `Surface (Sconce)`, and `Surface (Pendant)`
|
|
|
|
### Fixture Labor (`<fixture-labor>`)
|
|
|
|
| Fixture Type | Labor |
|
|
|:------------ | ----------:|
|
|
| Paddle Fan | 1.5 hr/ea. |
|
|
| Pendant | 1-4 hr/ea. |
|
|
| Tape | 0.5 hr/6ft |
|
|
| Site Poles | 1.5 hr/ea. |
|
|
| Festoon | 2.0 hr/ea. |
|
|
| All Others | 1.0 hr/ea. |
|
|
|
|
`FIXTURES`/`FIXTURE LABOR`/`FIXTURE LABOR 1HR`
|
|
|
|
### Wiring Method (`<wiring-method>`)
|
|
|
|
#### Conduit/Cable Type
|
|
|
|
#### Wire Size
|
|
|
|
| Case | Wire Size |
|
|
| -------------- | --------- |
|
|
| Site/Courtyard | #10 |
|
|
| Garage | #10 |
|
|
| NM Cable | #14\* |
|
|
| All Others | #12 |
|
|
|
|
\*Minimum #12 in kitchens and bathrooms.
|
|
|
|
#### Dimming Conductors
|
|
|
|
### Branch Length (`<branch-length>`)
|
|
|
|
| Case | Standard Length |
|
|
| --------------------- | --------------- |
|
|
| Site/Courtyard | 50ft |
|
|
| Garage | 50ft |
|
|
| BOH | 40ft |
|
|
| Corridors | 40ft |
|
|
| Interior Amenity | 40ft |
|
|
| Office/Retail | 50ft |
|
|
| Exterior Amenity | 50ft |
|
|
| Units | 20ft |
|
|
| Undercabinet Fixtures | 10ft |
|
|
| Stairwells | 20ft |
|
|
| Kitchen | ? |
|
|
|
|
Reduce as appropriate.
|
|
|
|
## Order
|
|
|
|
Use empty designations to separate phases.
|
|
|
|
> [!example]
|
|
> ```
|
|
> # Stairwells
|
|
> BS - Surface = 1.0hrs - #12 EMT 20ft
|
|
> # Building
|
|
> ## Units - Key
|
|
> UK - Surface = 1.0hrs - #12 MC+LV 20ft
|
|
> UK - Surface = 1.5hrs - #12 MC+LV 20ft
|
|
> UK - Surface (Pendant) = 2.0hrs - #12 MC+LV 20ft
|
|
> UK - Surface (J-Box For Future Fixture) = 1.0hrs - #12 MC+LV 20ft
|
|
> UK - Recessed = 1.0hrs - #12 MC+LV 20ft
|
|
> _
|
|
> ## Units - Residential
|
|
> UR - Surface (Tape) = 1.0hrs - #12 MC+LV 25ft
|
|
> UR - Surface (Wall) = 1.0hrs - #12 MC+LV 25ft
|
|
> ...
|
|
> ```
|
|
|
|
## Content
|
|
|
|
## Garage
|
|
|
|
Use ENT assemblies unless forbidden by spec.
|
|
|
|
| Case | Subassembly Path (`FIXTURE ACCESSORIES`/`PVC/ENT ASSEMBLIES`/...) |
|
|
|:----------------- | ----------------------------------------------------------------- |
|
|
| Conventional Slab | .../`GARAGE FIXTURE ENT W/#10 - STEEL OCT RING` |
|
|
| Precast/I-Beam | .../`GARAGE FIXTURE W/T ROD ENT W/#10 - STEEL OCT RING` |
|
|
|
|
If PVC is required, use following assemblies:
|
|
|
|
| Case | Subassembly Path (`FIXTURE ACCESSORIES`/`PVC/ENT ASSEMBLIES`/...) |
|
|
|:------- |:----------------------------------------------------------------- |
|
|
| Ceiling | .../`... - SLAB BOX / 45 DEG STUBBY` |
|
|
| Wall | .../`... - STL BOX & TILE RING / 45 DEG STUBBY/ ENT DROP` |
|
|
|
|
## Surface Mount
|
|
|
|
> [!info] Surface Mount Fixtures
|
|
> * Wall Mount
|
|
> * Wall Pack
|
|
> * Sconce
|
|
> * Swing Arm
|
|
> * Pendant
|
|
> * Linear
|
|
> * Tape
|
|
> * Track
|
|
|
|
| Wiring Method | Subassembly Path |
|
|
|:-------------- |:----------------------------------------------------------- |
|
|
| NM Cable | `NM ASSEMBLIES`/`RND BOX BAR HNGR...` |
|
|
| MC Cable | `MC ASSEMBLIES`/`SQ BOX, ROUND P RING & MNTG BRKT...` |
|
|
| PVC in Ceiling | `PVC/ENT ASSEMBLIES`/`... - SLAB BOX / 45 DEG STUBBY` |
|
|
| PVC in Wall | `PVC/ENT ASSEMBLIES`/`3/4" PVC W/ 3#12 - STL BOX/TILE RING` |
|
|
| EMT | `EMT ASSEMBLIES`/`... - SQ BOX & ROUND P RING` |
|
|
|
|
> [!note]
|
|
> Use lighting control cable assemblies in Amenity areas
|
|
|
|
### Tape Lighting
|
|
|
|
Also called "cove" or "strip" lighting,
|
|
however those terms are less specific
|
|
and potentially confusing.
|
|
|
|
Use item `FIXTURE LABOR 1HR`
|
|
and change `Fct 1` to match the calculated labor
|
|
(1 hour per 12 feet).
|
|
|
|
> [!note]
|
|
> Tape lighting length is limited by the "max power length" of the model
|
|
> (usually measured in millimeters).
|
|
> Max power length is usually 5000-15000mm (~16-49ft)
|
|
> depending on luminous output and voltage.
|
|
>
|
|
> A reasonable [[heuristics|rule of thumb]] is
|
|
> * _12V strips:_ 5m (16.4ft)
|
|
> * _24V strips:_ 10m (32.8ft)
|
|
|
|
Separate these fixtures by labor, not length
|
|
|
|
```
|
|
*** Back of House ***
|
|
B - Surface (Tape) = 1.0hr (0-17ft) - #12 MC 40ft
|
|
_
|
|
*** Interior Amenity ***
|
|
IA - Surface (Tape) = 1.0hr (00-17ft) - #12 MC+LV 40ft
|
|
IA - Surface (Tape) = 2.0hr (18-29ft) - #12 MC+LV 40ft
|
|
IA - Surface (Tape) = 3.0hr (30-41ft) - #12 MC+LV 40ft
|
|
IA - Surface (Tape) = 4.0hr (42-53ft) - #12 MC+LV 40ft
|
|
IA - Surface (Tape) = 5.0hr (54-65ft) - #12 MC+LV 40ft
|
|
IA - Surface (Tape) = 6.0hr (66-77ft) - #12 MC+LV 40ft
|
|
IA - Surface (Tape) = 7.0hr (78-89ft) - #12 MC+LV 40ft
|
|
```
|
|
|
|
## Recessed
|
|
|
|
> [!info] Recessed Fixtures
|
|
> * recessed downlight
|
|
> * recessed linear
|
|
> * wall grazer
|
|
> * troffer
|
|
|
|
| Wiring Method | Subassembly Path |
|
|
|:------------- |:------------------------------ |
|
|
| NM Cable | `NM ASSEMBLIES`/`HI HAT - ...` |
|
|
| MC Cable | `MC ASSEMBLIES`/`HI HAT - ...` |
|
|
|
|
For crowded puck light areas:
|
|
measure length between fixtures,
|
|
round up to the nearest 5ft
|
|
|
|
> [!note]
|
|
> "HI HAT" refers to a recessed can fixture.
|
|
|
|
## Undercabinet Fixtures
|
|
|
|
| Wiring Method | Subassembly Path |
|
|
|:------------- |:------------------------------------- |
|
|
| NM Cable | `NM ASSEMBLIES`/`UNDER CABINET - ...` |
|
|
| MC Cable | `MC ASSEMBLIES`/`UNDER CABINET - ...` |
|
|
|
|
> [!note]
|
|
> Takeoff 2 fixtures if jumping over oven
|
|
|
|
## Paddle Fans
|
|
|
|
| Wiring Method | Subassembly Path |
|
|
|:------------- |:----------------------------------------------------- |
|
|
| NM Cable | `NM ASSEMBLIES`/`RND BOX BAR HNGR...` |
|
|
| MC Cable | `MC ASSEMBLIES`/`FAN RATED OCT BOX W/ BAR HNGR - ...` |
|
|
| PVC | `PVC/ENT ASSEMBLIES`/`... - SLAB BOX / 45 DEG STUBBY` |
|
|
|
|
## Guardrail Fixtures
|
|
|
|
> [!info] Designation Subassemblies
|
|
`FIXTURE ACCESSORIES`/`COURTYARDS & LANDSCAPE`/`ALUM BOX W/ FLEX FIX, 3/4" CONDUIT - PVC40 - ...`
|
|
|
|
## Stairwells & Elevators
|
|
|
|
> [!info] Designation Subassemblies
|
|
> 1. `PVC/ENT ASSEMBLIES`/`... - SLAB BOX / 45 DEG STUBBY`
|
|
|
|
## Facade
|
|
|
|
> [!info] Breakdowns
|
|
> * `Phase` = "Facade"
|
|
|
|
Length and Labor will be more than a normal fixture in BOH/Amenity
|
|
|
|
| Fixture Type | Labor |
|
|
|:------------ |:---------------------- |
|
|
| Non-Linear | 2hrs |
|
|
| Linear | See [[#Tape Lighting]] |
|
|
|
|
> [!info] Designation Subassemblies
|
|
> 1. `3/4" PVC W/ 3#10 - STL BOX & TILE RING / 45 DEG STUBBY/ ENT DROP`
|
|
> * `Length per Unit` = Distance to panel
|
|
|
|
## Porte Cochere (Drive up Area)
|
|
|
|
Create its own breakout in WBS, and phase in [[accubid|Accubid]]
|
|
|
|
## Site & Courtyard
|
|
|
|
> [!important]
|
|
> Coordinate with landscape drawings
|
|
|
|
### Breakdowns
|
|
|
|
> [!info] Breakdowns
|
|
> * `System` = "FML - Site Fixtures Material & Labor"
|
|
|
|
### Pole Lights
|
|
|
|
> [!info] Designation Subassemblies
|
|
> 1. `FIXTURE ACCESSORIES`/`SITE POLE ASSEMBLIES`/...
|
|
|
|
Add subassemblies for stub-outs, pole, base, and grounding as appropriate.
|
|
|
|
### Festoon Lighting
|
|
|
|
> [!info] Also Known As
|
|
> * string lighting
|
|
> * market lighting
|
|
> * catenary lighting
|
|
|
|
> [!info] Designation Subassemblies
|
|
> 1. `FIXTURE LABOR`/`FIXTURE LABOR 2HR`
|
|
>
|
|
> 2. `FESTOON & ROOF ASSEMBLIES`/`FESTOON CABLE HANGER & EYE BOLTS - LENGTH`
|
|
> * **Length per Unit** = Light string length
|
|
>
|
|
> 3. `COURTYARDS & LANDSCAPE`/`ALUM BOX W/ FLEX FIX, 3/4" CONDUIT - PVC40 - ...`
|
|
> * **Length per Unit** = Distance to panel + 15ft
|
|
|
|
### Other Fixture Types
|
|
|
|
| Fixture Type | Subassembly Path (`FIXTURE ACCESSORIES`/`COURTYARDS & LANDSCAPE`/...) |
|
|
|:------------------------------------ |:--------------------------------------------------------------------- |
|
|
| Step Light | .../`STEP FIX, 3/4" CONDUIT - PVC40 - ...` |
|
|
| Bollard | .../`BOLLARD, 3/4" CONDUIT - PVC40 - ...`\* |
|
|
| Up-light | .../`PERMA POST, 3/4" CONDUIT - PVC40 - ...` |
|
|
| In-grade up-light | .../`3/4" CONDUIT - PVC40, IMC Elbow, ...` |
|
|
| Fixtures built into cabanas/pergolas | .../`ALUM BOX W/ FLEX FIX, 3/4" CONDUIT - PVC40 - ...` |
|
|
| Handrail light | .../`ALUM BOX W/ FLEX FIX, 3/4" CONDUIT - PVC40, IMC ELBOW - ...` |
|
|
|
|
\*If we don't own concrete, delete pre-cast bollard base from assembly
|
|
|
|
## FAA Lighting
|
|
|
|
> [!info] Designation Subassemblies
|
|
> 1. `FIXTURE LABOR`/`FIXTURE LABOR 1HR`
|
|
> 2. `FESTOON & ROOF ASSEMBLIES`/`Aircraft Warning, 3/4" Conduit GRC/PVC 2#10, 1#10G`
|