# Wiring Methods Selection
Seek to use the cheapest method,
as determined by Senior Construction Estimator
and Database Administrator,
as allowed for the situation.
![[pre-takeoff-research#Requirement Precedence]]
## By Construction Type
See [[ibc-construction-types]] for more info.
### Construction Types I, II
Nonmetallic-sheathed cables (NM, SE, etc.)
are not fire code permissible in these types.
PVC < MC < EMT < IMC < RMC
### Construction Types III, IV, V
NM/SE < PVC < EMT < IMC < RMC
## By Wiring Method
### Electrical Metallic Tubing (EMT)
#### Fittings
Set-screw < compression
> [!info]
> EMT has a third coupling type "indenter",
> which are crimped onto the conduit using a special tool.
> These are usually only mentioned in specifications
> to say that they are unacceptable.
> [!info] Edge Case: Vanderbilt Central Neighborhood Residential College
>
> > [!cite] Vanderbilt Central Neighborhood Residential College - Project Specifications (pp.)
> > Fittings for Type EMT Duct Raceways:
> > * Coupling Method: Compression coupling or Setscrew coupling.
> > Setscrew couplings with only single screw per conduit are unacceptable.
>
> > [!quote] Joel Jansen via Microsoft Teams @ 2025-10-15 09:33 AM
> > use set screw 🙂
### Rigid Polyvinyl Chloride Conduit (PVC)
Not usually permissible exposed indoors in any construction,
except in Florida.
May require rigid stub-ups in certain cases,
which could make EMT more cost-effective.
Consult with the Senior Construction Estimator in this case.
## By Use-Case
### Multi-Circuit Homeruns
> [!quote] Art Baldwin (pp.)
> Multi-circuit MC is not cost-effective
> when considering the difficulty of rework.
> Use conduit, even EMT if necessary.
## By Market Type
### Assisted Living
MC-AP may be required.
## Searching Specifications
> [!info] Example Specs Relevant to Wiring Methods Selection
> * 26XXXX - Raceway And Boxes For Electrical Systems
> * 26XXXX - Conduits For Electrical Systems
> * 26XXXX - Underground Ducts And Raceways For Electrical Systems
>
> * 26XXXX - Low-Voltage Electrical Power Conductors And Cables
>
> * 26XXXX - General Requirements For Electrical
> * 26XXXX - Common Work Results For Electrical