980 B
980 B
id, aliases, tags, title
| id | aliases | tags | title |
|---|---|---|---|
| Fire Resistive Wiring Methods |
Fire Resistive Wiring Methods
Requirements
Permitted methods for fire protection of emergency feeders are specified in 700.10(D)(1).
!nfpa-70_700_emergency-systems#700.10(D)(2) Feeder-Circuit Wiring.
the requirements of which only apply to occupancies listed in 700.10(D)(1)
!nfpa-70_700_emergency-systems#700.10(D)(1) Occupancies.
Note that even in these occupancies only nfpa-70_100_definitions#Feeder. require fire protection, not nfpa-70_100_definitions#Branch Circuit..
Construction
[!info] Keywords
- Low Smoke Zero Halogen (LSZH)
- Mineral Insulated (MI) Cable
- Fire Resistive Metal-Clad (MC) Cable
- Fire Resistive Cable-in-Conduit (CIC)
[!info] "Vitalink" vs "Lifeline" cable VITALink® and Lifeline® are brand names (of Omni Cable and Prysmian Group respectively), not cable types. Both brands include MC and CIC cables.