# 2026-03-09 15:50:49
## Pre-Takeoff Confirmation --- Charlotte South End Hotel
%%
Implementation of [[conest-pre-takeoff-email-template]]
for [[charlotte-south-end-hotel]]
%%
Hello Team,
Below is a comprehensive list of means & methods
for **Charlotte South End Hotel**.
Please confirm you have received this email
and respond with any questions or comments.
* **Delivery Method:** Plans & Specs
* **Document Stage:** Issue for Permit
* **Drawings Date:** 2026-02-27
* **Project Manual Date:** 2026-02-27
* **Proposal Date:** 2025-12-12
* **Takeoff Request Stage:** Full Takeoff
### Project Specification Callouts
* **Conduit:**
* EMT Fittings: _---Spec 260510 2.4(N)(2) (p. 2226)_
* Smaller than trade size 2-1/2": Compression
* Trade size 2-1/2" and larger: Set-screw
* **Wire:**
* Material: Aluminum 1 AWG and larger _---Spec 260510 2.2(C)(1) (p. 2224)_
* Acceptable Manufacturers: _---Spec 260510 2.2(D) (p. 2224)_
* Encore Wire
* General Cable
* Okonite
* Paranite
* Pirelli
* Senator
* Southwire
* **MC Cable:**
* Application: "dry locations only where approved by code authority."
_---Spec 260510 2.4(N)(8) (p. 2227)_
* Acceptable Manufacturers: _---Spec 260510 2.2(E) (p. 2224)_
* Alflex
* AFC
* America Metal Moulding
* Encore Wire
* Southwire
* **Steel Box Depth:** Not specified _---Spec 260510 2.12(A) (p. 2231)_
* **Floor Boxes:** _---Spec 260510 2.12(E) (p. 2231)_
* Box Material:
* Slab on grade: Cast iron
* Slabs above grade: Stamped steel
* Cover Material: Not specified.
* **Wiring Devices:**
* All Areas:
* Current rating: 20A _---Spec 260510 2.16(B)(1) (p. 2231)_
* Standard/Decora: Decora _---Spec 260510 2.16(D) (p. 2231)_
* **Switchboards:**
* Bus Material: "aluminum or copper, tin or silver plated" _---Spec 262000 2.6(C)(4) (p. 2297)_
* OCPD Interrupting Current Ratings: Not specified.
* Acceptable Manufacturers: _---Spec 262000 2.17(C) (p. 2307)_
* Eaton
* ABB/GE
* Schneider Electric
* Siemens
* **Panelboards:**
* Bus Material: "silver plated copper or electro-tin plated aluminum"
_---Spec 262000 2.8(E) (p. 2303)_
* Breaker Types: Bolt-on _---Spec 262000 2.9(C) (p. 2303)_
* OCPD Interrupting Current Ratings:
* Distribution Panelboards: Not specified.
* Lighting and Appliance Panelboards: Not less than 10kAIC
_---Spec 262000 2.10(A)(3) (p. 2304)_
* Acceptable Manufacturers: _---Spec 262000 2.17(C) (p. 2307)_
* Eaton
* ABB/GE
* Schneider Electric
* Siemens
* **Transformers:**
* Winding Material:
"Transformer windings shall be manufacturer's standard design,
copper or aluminum conductor. Bussing shall be copper."
_---Spec 262002.5(L) (p. 2296)_
* K-Rating: Only as shown (None shown)
_---Spec 262002.5(K) (p. 2295)_
* Acceptable Manufacturers: _---Spec 262000 2.17(D) (p. 2307)_
* Eaton
* ABB/GE
* Heavy Duty
* MGM
* Siemens
* Schneider Electric
* United Power Corp
* **Generator:** (1) 500kW Diesel _---Dwg. E05-12_
* Enclosure Specs: Not specified.
* Remote Tank: None shown or specified.
* Tank Size: 12hrs at full load _---Spec 263213 2.7(C) (p. 2326)_
* Load Banks: None shown or specified.
* Acceptable Manufacturers: _---Spec 263213 2.1(A) (p. 2323)_
* Caterpillar Tractor Co.
* Cummins/Power Generation
* Kohler Power Systems (MTU Engine Only)
* MTU On-Site Energy
### Project Drawing/Detail Callouts
* Describe conflicts between drawings / proposal:
%% "Plans show CU feeders, proposal calls for aluminum", Specification grade devices, etc. %%
* Cost drivers in details not shown elsewhere on plans:
### PDI System Execution Plan
* **Primaries:** Conduit only; wiring, duct bank by others.
* **Secondaries:** Aluminum bus duct. _---Spec 262000 2.11(D) (p. 2305)_
%% PVC UG, GRC Stub-ups, AL %%
* **Feeders:**
PVC UG, EMT OH.
Size and material per E05-10 schedule
(AL 100A and larger,
==transformer primaries and secondaries all copper==).
Voltage drop not considered
(allowance per E00-00, "GENERAL PRICING NOTES").
%% PVC UG, EMT OH, AL over 100A, 2% VD %%
%% Emergency Feeds MI Cable %%
* **Unit Subfeeds:**
#12 Multi-Circuit MC OH.
Voltage drop not considered
(allowance per E00-00, "GENERAL PRICING NOTES").
%% MC OH AL, VD per Chart on E5.01 %%
%% [[2026-03-10_13-51-32#Voltage Drop]] %%
* **Units:**
* VFCU HVAC
* 20A Decora Switches
* 20A Decora Receptacles
* Master Switch control
* Floor boxes (0--1 per K, QQ unit; 2 per 2B, 3B unit)
%% 15A Decora, Disposals, T-stat, Floor Boxes, Shade Control, Doorbells, Dimmer Switches, etc. %%
* **Telecom:**
Rough-in only, system alternate.
Free-air where allowed by code.
EMT Risers.
* **EV Chargers:** Excluded (alternate).
%% (42) Conduit only, (56) Conduit & Wire, (20) Conduit, Wire & Equipment %%
%% [[2026-03-10_13-51-32#EV Chargers]] %%
* **Fire Alarm:**
Free-air where allowed by code.
EMT Risers.
* **DAS:**
Rough-in only, per PDI DAS Design.
* **Low Voltage:**
Free-air where allowed by code.
Stub-ups to accessible ceilings.
_---Proposal 2025-12-12 Ex. B Notes_
### Lighting Control
%% [[2026-03-10_13-51-32#Lighting Control]] %%
* **Applicable Code:**
2024 North Carolina Energy Conservation Code
(2021 IECC with NC Amendments)
_---Dwg. G00-11_
* **Basis of Takeoff:** Central dimming system per P&S, PDR quote.
* **By Area:**
* Units: Master Switch, Digital Standalone Control, 0-10V dimming.
* Amenity: Digital Central Control, 0-10V dimming.
* Corridors: 0-10V dimming per 2021 IECC and LEED checklist.
* BOH: Line voltage control.
* Garage: Line voltage control (integral dimming occupancy sensors).
%% Assign Method to Areas: Line Voltage, Low-Voltage Stand Alone or Centralized System %%
### Tasks/Quotes Needed for WBS
%%
Only tasks that are not already open.
%%
* DAS Public Safety Raceway Design
%% Necessary because we own DAS pathways but not the system %%
%%
* Electrical Constructability Review
* Electrical VDC
* Coordination Study
%%
Thank you,