4.5 KiB
id, aliases, tags
| id | aliases | tags | |
|---|---|---|---|
|
Fire Alarm
Sequence
1. Estimate preparation
- Initial the OneNote
- Read about the project specifications and construction type
- Find Fire Alarm plans (if present)
- Locate the following rooms:
- Fire Command Center (FCC)
- Generator Room
- Fire Pump Room
- Elevator Control Rooms
- Elevator Shafts
- Stairwells
2. Takeoff
Riser
Fire Command Center
{Building Type} Head End CA.30.23.X
Generator Room
CA.30.22.2
Fire Pump Room
CA.30.22.4
FACR to Elevator Shafts
Elevator Shafts (CA.30.22.8)
FACR TO ELEV SHAFT 1 ½" (CA.30.22.10/11)
Measure Length from the most distant points of the FACR and each shaft. Input adder length to reach the bottom of the pit (Minimum 15ft adder).
| 1 shaft | 2 shafts |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| ||=======================|| | ||============||============|| |
| | |
FACR to Elevator Control Rooms
Elevator Control Room (CA.30.22.6)
FACR/FCC TO ELEV CONTROL ROOM (CA.30.22.13/14)
- Measure the Horizontal and Vertical Distance from the FACR to the ECR.
- Use Typicals for the vertical riser. (Ex// 10' per floor)
FACR to Stairwells
FACR TO STAIRWELLS 1" PVC (CA.30.22.17)
-
Measure from the furthest end of FACR to the furthest end of the stairwell to find length
-
This is for the Flow/Tamper modules in the stairwells
Terminal Cabinets
TERMINAL CABINETS (2) 2" EMT/PVC (CA.30.26. __)
Horizontal:
- Measure from the Fire Command room to all electrical rooms
Vertical:
- Use 10ft Riser in Typical
- GA or HD - 1" conduit / HR - (2) 2" conduits)
Annunciator Panels
- Fire Alarm Annunciator (FAA),
- Fire Alarm Annunciator Panel (FAAP)
ANNUNCIATORS (CA.30.27.2/3)
Remote Serial Annunciator, LCD Display - PVC
- Measure from the Fire Command Room to FAA or Lobby
Sleeving
Devices
- Takeoff floor plans in order
- Takeoff enlarged drawings
Smoke Detectors
Design Build: Count every stairwell at every level.
Pull Stations
Design Build: Count every stairwell at every level and every exterior exit.
Flow-Tamper Switches
No free air. if wood frame, take off as EMT.
Design Build: Count every stairwell at every level.
Magnetic Door Holders
Mech Connection - PVC AL Flex - 20 A
Design Build: Count every set of double doors. (Typical of elevator lobbies and corridors)
Speaker Strobes
Design Build:
- Count every 75 ft,
- measure with circles on Bluebeam
- or divide relevant SF area by 4415
\pi(\frac{75}{2})^2 \approx 4415
- every elevator lobby,
- and every BOH room on the first floor and garage levels.
Fire Smoke Dampers (FSD's)
Take off both FA and Electrical
- Misc Assemblies
Area of Refuge (AoR) / Two-Way
PROPOSAL "STAND ALONE SYSTEMS"
CA.31.27. 4/7
Horizontal
Take off once
- Length:
- If shown on Plans (FA/Systems/ etc.)
- based on FCR to Elevator Lobbies & FCR to Stairwells* (Whichever is longer)
- Count: Number of boxes run to. If not shown, use the largest count between Elev. & Strwlls.
Vertical
Typical on all floors
- Length: 15ft x per count
- Count: match Horizontal
Responder Radio / DAS
FACR to Every Elev. Shaft
FACR TO ELEV PIT = 2" PVC40 CA.28.31.5
Match Fire Alarm takeoff Length and Count
FACR to Every Staircase
FACR TO STAIRWELL = 2" PVC40 CA.28.31.8
Match Fire Alarm takeoff Length and Count
Stairwell Riser Every 2 Floors
STAIRWELL RISER EVERY 2 FLRS = 1 1/2" EMT (20') W/ 16X16X6 BOX CA.28.31.12
Create a Stairwell typical on every other floor
FACR to Electric Room
FACR TO 2HR-RATED RM = 2" PVC40 CA.28.31.14
Match Fire Alarm takeoff Length
Electric Room Riser to Every Floor
2HR-RATED RM RISER TO EVERY FLR = 2" EMT (15') W/ 16X16X6 BOX CA.28.31.18
Takeoff in every Electric Room
Top 2H Rated Room To Roof
FACR TO ROOF = 2" EMT W/ RMC WEATHERHEAD & IMC STUB CA.28.31.18
Use 15' or Height of ceiling on last building level
Horizontal
CORRIDORS EMT OH = 1 1/2" EMT W/ 16X16X6 BOX EVERY 80' CA.28.31.23
CORRIDORS DECK = 1 1/2" PVC40, STUBBY, FLEX W/ 16X16X6 BOX EVERY 80' CA.28.31.21
1-1/2 through corridors w/ 16x16x6 J-Box
Length for every corridor/garage
3. Extension (Review and Checking)
- Sleeving