Sequence

1. Estimate preparation

  1. Initial the OneNote
  2. Read about the project specifications and construction type
  3. Find Fire Alarm plans (if present)
  4. Locate the following rooms:
    • Fire Command Center (FCC)
    • Generator Room
    • Fire Pump Room
    • Elevator Control Rooms
    • Elevator Shafts
    • Stairwells

2. Takeoff

Riser

Fire Command Center

{Building Type} Head End CA.30.23.X

Generator Room

CA.30.22.2

Fire Pump Room

CA.30.22.4

FACR to Elevator Shafts

Elevator Shafts (CA.30.22.8)

FACR TO ELEV SHAFT 1 ½" (CA.30.22.10/11)

Measure Length from the most distant points of the FACR and each shaft. Input adder length to reach the bottom of the pit (Minimum 15ft adder).

|           1 shaft           |            2 shafts            |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| ||=======================|| | ||============||============|| |
|                             |                                |
FACR to Elevator Control Rooms

Elevator Control Room (CA.30.22.6)

FACR/FCC TO ELEV CONTROL ROOM (CA.30.22.13/14)

  • Measure the Horizontal and Vertical Distance from the FACR to the ECR.
  • Use Typicals for the vertical riser. (Ex// 10' per floor)
FACR to Stairwells

FACR TO STAIRWELLS 1" PVC (CA.30.22.17)

  • Measure from the furthest end of FACR to the furthest end of the stairwell to find length

  • This is for the Flow/Tamper modules in the stairwells

Terminal Cabinets

TERMINAL CABINETS (2) 2" EMT/PVC (CA.30.26. __)

Horizontal:

  • Measure from the Fire Command room to all electrical rooms

Vertical:

  • Use 10ft Riser in Typical
  • GA or HD - 1" conduit / HR - (2) 2" conduits)
Annunciator Panels
  • Fire Alarm Annunciator (FAA),
  • Fire Alarm Annunciator Panel (FAAP)

ANNUNCIATORS (CA.30.27.2/3)

Remote Serial Annunciator, LCD Display - PVC

  • Measure from the Fire Command Room to FAA or Lobby
Sleeving

Devices

  1. Takeoff floor plans in order
  2. Takeoff enlarged drawings
Smoke Detectors

Design Build: Count every stairwell at every level.

Pull Stations

Design Build: Count every stairwell at every level and every exterior exit.

Flow-Tamper Switches

No free air. if wood frame, take off as EMT.

Design Build: Count every stairwell at every level.

Magnetic Door Holders

Mech Connection - PVC AL Flex - 20 A

Design Build: Count every set of double doors. (Typical of elevator lobbies and corridors)

Speaker Strobes

Design Build:

  • Count every 75 ft,
    • measure with circles on Bluebeam
    • or divide relevant SF area by 4415
      • \pi(\frac{75}{2})^2 \approx 4415
  • every elevator lobby,
  • and every BOH room on the first floor and garage levels.

Fire Smoke Dampers (FSD's)

Take off both FA and Electrical

  • Misc Assemblies

Area of Refuge (AoR) / Two-Way

PROPOSAL "STAND ALONE SYSTEMS"

CA.31.27. 4/7

Horizontal

Take off once

  • Length:
    • If shown on Plans (FA/Systems/ etc.)
    • based on FCR to Elevator Lobbies & FCR to Stairwells* (Whichever is longer)
  • Count: Number of boxes run to. If not shown, use the largest count between Elev. & Strwlls.
Vertical

Typical on all floors

  • Length: 15ft x per count
  • Count: match Horizontal

Responder Radio / DAS

FACR to Every Elev. Shaft

FACR TO ELEV PIT = 2" PVC40 CA.28.31.5

Match Fire Alarm takeoff Length and Count

FACR to Every Staircase

FACR TO STAIRWELL = 2" PVC40 CA.28.31.8

Match Fire Alarm takeoff Length and Count

Stairwell Riser Every 2 Floors

STAIRWELL RISER EVERY 2 FLRS = 1 1/2" EMT (20') W/ 16X16X6 BOX CA.28.31.12

Create a Stairwell typical on every other floor

FACR to Electric Room

FACR TO 2HR-RATED RM = 2" PVC40 CA.28.31.14

Match Fire Alarm takeoff Length

Electric Room Riser to Every Floor

2HR-RATED RM RISER TO EVERY FLR = 2" EMT (15') W/ 16X16X6 BOX CA.28.31.18

Takeoff in every Electric Room

Top 2H Rated Room To Roof

FACR TO ROOF = 2" EMT W/ RMC WEATHERHEAD & IMC STUB CA.28.31.18

Use 15' or Height of ceiling on last building level

Horizontal

CORRIDORS EMT OH = 1 1/2" EMT W/ 16X16X6 BOX EVERY 80' CA.28.31.23

CORRIDORS DECK = 1 1/2" PVC40, STUBBY, FLEX W/ 16X16X6 BOX EVERY 80' CA.28.31.21

1-1/2 through corridors w/ 16x16x6 J-Box

Length for every corridor/garage

3. Extension (Review and Checking)

  • Sleeving