215 lines
13 KiB
Markdown
215 lines
13 KiB
Markdown
---
|
|
id: 2026-05-14T08:46:17-0400
|
|
title: 2026-05-14 08:46:17
|
|
tags:
|
|
- exclude-from-word-count
|
|
daily: "[[2026-05-14]]"
|
|
---
|
|
# 2026-05-14 08:46:17
|
|
|
|
Electrical specifications for [[303-mariposa-residence]]
|
|
|
|
# E3.0 - SPECIFICATIONS
|
|
|
|
## SECTION 16010 - BASIC ELECTRICAL REQUIREMENTS
|
|
|
|
### 1) PART 1 GENERAL
|
|
|
|
#### a) POWER AND CONTROL WIRING
|
|
|
|
* i) Provide power system conduit and wiring to mechanical equipment. Controls system conduit and wiring for mechanical systems is included under Division 15. “Power” wiring includes line voltage wiring from distribution apparatus to disconnecting means provided or installed under this section, and from such disconnecting means to motors, and to terminal boxes of 'package' equipment. “Controls” wiring includes wiring, regardless of voltage, which provides start-stop control for mechanical equipment and/or which is used to monitor functions of mechanical systems. Where line voltage wiring is extended from a local disconnecting means to relays, thermostats, by-pass timers, starter coils or the like, or from mechanical control panels or motor control centers to control devices, such extensions are considered “control” wiring.
|
|
|
|
#### b) MOUNTING HEIGHTS
|
|
|
|
* i) Mounting heights and locations: verify the exact location of equipment with architect prior to installation. Wall mounted devices requiring operational access shall be mounted a minimum of 15 inches above finished floor to bottom of device and a maximum of 48 inches above finished floor to top of device. Visual alarms shall be mounted not less than 80 inches to the bottom or 96 inches to the top of the device.
|
|
|
|
#### c) REGULATORY REQUIREMENTS
|
|
|
|
* i) Conform to:
|
|
|
|
* (1) NFPA-70 - National Electric Code.
|
|
|
|
* ii) Comply with the current applicable codes, ordinances, and regulations of the authority or authorities having jurisdiction, the Owner's insurance underwriter, and applicable base building standards.
|
|
|
|
* iii) When conflict exists between two or more governing codes, comply with the stricter requirement.
|
|
|
|
* iv) Obtain permits, and request inspections from authority having jurisdiction.
|
|
|
|
#### d) PROJECT/SITE CONDITIONS
|
|
|
|
* i) Install Work in locations shown on Drawings, unless prevented by Project conditions. Coordinate installation of work in available space with work furnished under other Divisions.
|
|
|
|
### 2) PRODUCTS
|
|
|
|
* a) Where manufacturer's model or series numbers are specified or shown, these indicate generally acceptable types required. Furnish products which comply with all requirements, as specified or shown.
|
|
|
|
* b) When more than one unit of the same class of equipment is required, provide units produced by a single manufacturer.
|
|
|
|
### 3) TESTS
|
|
|
|
* a) Furnish test equipment, facilities, and technical personnel required to perform field tests.
|
|
|
|
* b) At completion of job, check voltage at several points of utilization on the system. Energize all loads installed.
|
|
|
|
### 4) CLEANING
|
|
|
|
* a) Clean all fixtures and equipment at the completion of the project. Wipe clean exposed lighting fixture reflectors and trim pieces with a non-abrasive cloth just prior to occupancy.
|
|
|
|
### 5) RECORD DRAWINGS
|
|
|
|
* a) Upon completion of the Work, deliver to Architect and up-to-date set of “as-built” record drawings on a reproducible medium including AutoCAD.
|
|
|
|
### 6) DEMOLITION
|
|
|
|
* a) Remove, relocate, and reroute existing electrical equipment to facilitate new construction or remodeling work.
|
|
|
|
* b) Examine the site to observe and note existing conditions prior to submitting a bid.
|
|
|
|
* c) Schedule demolition in advance. Schedule work to avoid disruption of normal operations.
|
|
|
|
* d) Reconnect circuits serving equipment required to remain in service to other panelboards, motor control centers, or other appropriate distribution equipment. Provide additional panelboards, motor control centers, or other appropriate distribution equipment where there is insufficient available capacity in remaining existing equipment for reconnection.
|
|
|
|
* e) Remove existing conduit and wire back to panelboard, motor control center, or other distribution source.
|
|
|
|
* f) Where a circuit is interrupted by removal of a device or fixture from that circuit, provide additional conduit and wire to restore service to the remaining devices and fixtures on that circuit.
|
|
|
|
* g) Electrical equipment to be removed that is in good working order shall be carefully removed and offered to the Owner. Items rejected by the Owner shall be removed from the project site and properly disposed of.
|
|
|
|
## SECTION 16100 - BASIC MATERIALS AND METHODS
|
|
|
|
### 1) PART 1 GENERAL
|
|
|
|
#### a) REFERENCES
|
|
|
|
* i) All equipment and installations shall meet or exceed minimum requirements of ADA, ANSI, ASTM, IEEE, IES, NEC, NEMA, NETA, NFPA, OSHA, SMACNA, UL, and the State Fire Marshal. Equipment shall be certified for use in the State of the project and shall meet the State energy code. Provide products and materials that are new, clean, free of defects, and free of damage and corrosion.
|
|
|
|
#### b) PERFORMANCE REQUIREMENTS
|
|
|
|
* i) Provide support system for equipment and conduit, including wiring, with a minimum safety factor of 4. For empty conduits, include weight of 4 type XHHW wires of maximum permissible size.
|
|
|
|
#### c) QUALITY ASSURANCE
|
|
|
|
* i) All equipment and installations shall meet or exceed minimum requirements of ADA, ANSI, ASTM, IEEE, IES, NEC, NEMA, NETA, NFPA, OSHA, SMACNA, UL, and the State Fire Marshal. Equipment shall be certified for use in the State of the project and shall meet the State energy code. Provide products and materials that are new, clean, free of defects, and free of damage and corrosion.
|
|
|
|
### 2) PART 2 PRODUCTS
|
|
|
|
#### a) CONDUIT
|
|
|
|
* i) General
|
|
|
|
* (1) Exposed Dry and Damp Locations:
|
|
|
|
* (a) Use electrical metallic tubing.
|
|
|
|
* (2) Concealed Locations:
|
|
|
|
* (a) Furred, Ceiling Spaces and Stud Walls: Use electrical metallic tubing.
|
|
|
|
* (b) Connections to Lighting Fixtures in Accessible Ceilings: Use flexible conduit.
|
|
|
|
* (3) Equipment Connections:
|
|
|
|
* (a) Connections to Liquid-Handling Equipment in Dry Locations: Use liquid-tight flexible conduit.
|
|
|
|
* (4) Equipment for Dry Systems in Dry Locations: Use flexible conduit.
|
|
|
|
* ii) Electrical Metallic Tubing:
|
|
|
|
* (1) Continuous, seamless steel tubing, galvanized or sherardized on exterior, coated on interior with smooth hard finish of lacquer, varnish or enamel, with steel, set screw or compression type fittings. Provide concrete type fittings where required.
|
|
|
|
* (2) Use for general purpose feeders and branch circuits.
|
|
|
|
* iii) Flexible Steel Conduit:
|
|
|
|
* (1) Single strip, continuous, flexible interlocked double-wrapped steel, hot dip galvanized inside and out forming smooth internal wiring channel, with steel, compression type fittings.
|
|
|
|
* (2) Use in dry locations only, connections to lighting fixtures in suspended ceilings, connections to equipment installed above suspended ceilings, transformer connections, busway plug in units, and connections to equipment where vibration isolation is required, maximum length of 6 feet.
|
|
|
|
* iv) Liquid Tight Flexible Steel Conduit:
|
|
|
|
* (1) Same as flexible steel conduit except with tough, inert, watertight plastic outer jacket. Fittings shall be cast malleable iron body and gland nut, cadmium plated with one-piece brass grounding bushings threaded to interior of conduit. Spiral molded vinyl sealing ring between gland nut and bushing and nylon insulated throat.
|
|
|
|
* (2) Use same as flexible steel conduit in damp or wet locations and at motor connections.
|
|
|
|
* iv) Non-metallic Building Wire (NM):
|
|
|
|
* (1) Type NM-B cable may be used for both exposed and concealed work in normally dry locations at temperatures not to exceed 90 degrees Centigrade (with ampacity limited to that for 60 degree Centigrade conductors) as specified in the National Electric Code. NM-B cable may be run in air voids of masonry block or tile walls where such walls are not subject to excessive moisture or dampness. Voltage rating of NM-B cable is 600-volts.
|
|
|
|
* v) Type SEU and SER Cable
|
|
|
|
* (1) Type SER and SEU cable shall be UL Listed Type as specified, suitable for operation at 600 volts or less as specified in the NEC. Conductors shall be aluminum alloy per ASTM B-801. Insulation type XHHW-2 cross linked polyethylene (XLP) insulation. Gray sunlight resistant polyvinyl chloride (PVC) jacket.
|
|
|
|
#### b) BUILDING WIRE AND CABLE
|
|
|
|
* i) Provide wire with a minimum insulating rating of 600 volts, except for wire used in low voltage (below 50 volts) control or signal systems. The use of teflon (multi-conductor) for low tension systems may be permitted for fire alarm, signal and communication systems (voice and data) as approved on shop drawings by engineers and where permitted by local codes and union practice.
|
|
|
|
* ii) Conductors
|
|
|
|
* (1) Electrical grade, annealed copper, and fabricated in accordance with ASTM standards. Minimum size number 12 AWG for branch circuits; number 14 AWG for control wiring.
|
|
|
|
* (2) Unless otherwise specified, all wires numbers 10 and smaller shall be solid.
|
|
|
|
* (3) All wires number 8 and larger shall be stranded in accordance with ASTM Class B stranding designations.
|
|
|
|
* (4) Control wires shall be stranded in accordance with ASTM Class B stranding designations.
|
|
|
|
* (5) Cables for low tension systems shall be multi-conductor, 16 gauge, color coded and insulated in armored cable assembly, with number of conductors as required.
|
|
|
|
* (6) All 600 volt wire and cables unless otherwise specified shall be single conductor suitable for use in wet and dry and locations.
|
|
|
|
* iii) Connectors
|
|
|
|
* (1) Make connections, splices, taps and joints with solderless devices, mechanically and electrically secure. Protect exposed wires and connecting devices with electrical tape or insulation to provide insulation values not less than on conductor.
|
|
|
|
* iv) Cables (No. 8 and Larger):
|
|
|
|
* (1) Use set screw or compression type connectors, taps and splices specifically designed for the particular connection. Insulate splice either by taping or by use of "Bakelite" covers designed to fit around splice.
|
|
|
|
* v) Branch Circuit Wires (Number 10 and Smaller): Use any of the following types of terminals and connecting devices:
|
|
|
|
* (1) Hand Applied: Coiled, tapered, spring wound devices with a conducting corrosion-resistant coating over the spring steel and a plastic cover and skirt providing full insulation for splice and wired ends. Screw connector on by hand.
|
|
|
|
* (2) Tool Applied: Steel cap, with conduction and corrosion resistant metallic plating, open at both ends, fitted around the twisted ends of the wire and compressed or crimped by means of a special die designed for the purpose. Specifically fitted plastic or rubber insulating cover wrap over each connector.
|
|
|
|
#### c) BOXES
|
|
|
|
* i) Pressed steel, galvanized or cadmium-plated, 4 inches minimum octagonal or square with galvanized cover or extension ring as required.
|
|
|
|
* ii) Back-to-back outlets in the same wall, or “through-wall” type boxes are not permitted. Provide 12 inch minimum spacing for outlets shown on opposite sides of a common wall. Provide acoustical potting compound on all outlet boxes.
|
|
|
|
#### d) WIRING DEVICES
|
|
|
|
* i) Switches and Receptacles: Arrow Hart, Hubbell, Leviton, Pass & Seymour, or Slater.
|
|
|
|
* ii) Wall Dimmers: Lutron.
|
|
|
|
* iii) Occupancy Sensors: Mytech, Novitas, or Watt Stopper.
|
|
|
|
* iv) Floor Boxes and Fittings:
|
|
|
|
* (1) Poke through type: Wiremold Legrand.
|
|
|
|
* (2) Recessed flush floor box type: Steel City or Wiremold Legrand.
|
|
|
|
* v) Plugstrip: Wiremold.
|
|
|
|
* vi) Device and cover plate colors shall be as selected by Architect.
|
|
|
|
#### e) SUPPORTS
|
|
|
|
* i) Support raceways on accepted types of wall brackets, specialty steel clips, or hangers, ceiling trapeze hangers, or malleable iron straps. Plumber's perforated straps are not permitted. Acceptable manufacturers' brackets or hangers are Kindorf, Elcan, Binkley, Multi-Frame, Power-Strut, or Unistrut. Do not suspend raceways or equipment from other raceways, steam, water, or other piping or ductwork, except as otherwise permitted. Provide independent and secure support methods.
|
|
|
|
#### f) PANELBOARDS
|
|
|
|
* i) Acceptable Manufacturers: Cutler-Hammer/Westinghouse, General Electric, Siemens, or Square D/Groupe Schneider.
|
|
|
|
* ii) AIC Rating: Branch panelboards and overcurrent protection devices shall have a minimum short circuit rating of 10,000 RMS symmetrical amperes minimum interrupting capacity (120/208V) or 14,000 RMS symmetrical amperes minimum interrupting capacity (277/480V).
|
|
|
|
* iii) AIC Rating: Distribution panelboards and overcurrent protection devices shall have a minimum short circuit rating of 42,000 RMS symmetrical amperes minimum interrupting capacity (120/208V) or 200,000 RMS symmetrical amperes minimum interrupting capacity (277/480V).
|
|
|
|
* iv) Enclosures: Corrosion resistant galvanized (zinc finished) sheet steel. Fronts shall be cold rolled steel, finish coated with ANSI 61 grey enamel over a rust inhibitor. Panel locks shall be keyed alike.
|
|
|
|
* v) Doors: One piece bolt on front with a lockable hinged door over the overcurrent protection devices.
|
|
|
|
* vi) Bus Bars: Silver plated aluminum or copper. Neutral bus shall be full size. Neutral bus shall be 200% rated when supplied from a double neutral feeder. Provide an equipment ground bus in each panelboard. In addition to the equipment ground bus, provide an isolated ground bus when supplied from a feeder which includes an isolated grounding conductor.
|
|
|