65 lines
1.5 KiB
Markdown
65 lines
1.5 KiB
Markdown
---
|
|
id:
|
|
aliases:
|
|
- 2-way-communication
|
|
- area-of-rescue
|
|
- two-way-communication
|
|
tags:
|
|
- occupational/systems/standalone-systems
|
|
- type/guide
|
|
---
|
|
# Area of Refuge (AoR)
|
|
|
|
## Info
|
|
|
|
> [!info] Also Known As
|
|
> * Area of Rescue
|
|
> * 2-Way Communication
|
|
|
|
### 2-Way vs. AoR
|
|
|
|
Area of Refuge is defined in NFPA 101 _Life Safety Code_.
|
|
|
|
In NFPA 101 "two-way communication system" is used as generic term,
|
|
to be installed in accordance with the governing code NFPA 72.
|
|
|
|
NFPA 72 _Fire Alarm and Signaling Code_, Chapter 24 _Emergency Communications Systems (ECS)_
|
|
|
|
24.8 Two-Way, In-Building Wired Emergency Services Communications Systems
|
|
|
|
24.10 Area of Refuge (Area of Rescue Assistance) Emergency Communications Systems,
|
|
Stairway Communications Systems, Elevator Landing Communications Systems,
|
|
and Occupant Evacuation Elevator Lobby Communications Systems.
|
|
|
|
## Sequence
|
|
|
|
### 1. Estimate preparation
|
|
|
|
Complete [[fire-alarm]] preparation and takeoff.
|
|
|
|
### 2. Takeoff
|
|
|
|
##### Horizontal
|
|
|
|
> Area: Same as Fire Command Room
|
|
|
|
`FIRE ALARM & DAS SYSTEMS`/`TWO WAY COMMUNICATION ASSEMBLIES`/`...`
|
|
|
|
* Length: Per drawings if shown, otherwise use longer of
|
|
* FCR to elevator lobbies
|
|
* FCR to stairwells
|
|
* Count: Number of boxes run to. Per drawings if shown, otherwise use the greater of:
|
|
* Count of elevators
|
|
* Count of stairwells
|
|
|
|
##### Vertical
|
|
|
|
> Area: "Typical - Building All Levels"
|
|
|
|
`FIRE ALARM & DAS SYSTEMS`/`TWO WAY COMMUNICATION ASSEMBLIES`/`...`
|
|
|
|
* Length: 15ft x per count
|
|
* Count: match Horizontal
|
|
|
|
### 3. Extension (Review and Checking)
|