Files
zmVault/conductor-sizing.md
T

180 lines
4.6 KiB
Markdown

---
id:
aliases: []
tags:
- destiny/fleeting
- status/incomplete
- topic/electrical
- type/encyclopedia
---
# Conductor Sizing
Conductors are sized to be suitable for the load,
overcurrent protection is sized to protect the conductors.
## "The 80% Rule"
"The 80% Rule" is a rule of thumb
referring to a common convention of several articles
including:
* [[nfpa-70_210_branch-circuits#210.19(A)(1) General.]]
* [[nfpa-70_215_feeders#215.2(A)(1) General.]]
* [[nfpa-70_430_motors#430.22 Single Motor.]]
which paraphrased states:
> ... the minimum conductor size shall have an ampacity
> not less than the noncontinuous load
> plus 125 percent of the continuous load
When the rule is repeated,
the noncontinuous load is ignored
and it is stated that conductors are suitable
for 80% their listed rating,
since 80% is the reciprocal of 125%.
## Branch Circuits
### Receptacle Branch
> [!important]
> There is no maximum number of receptacles per circuit _in any occupancy_.
It is a common misconception that the limit
can be calculated with a formula like
$$
\frac{1.25(180VA)}{120V} = 1.875A, \quad \frac{20A}{1.875A} = 10.\bar{6}
$$
but the 180VA per yoke load specified in
[[nfpa-70_220_load-calculations#220.14(I) Receptacle Outlets.|220.14(I)]]
is specifically for calculating service and feeder sizing.
Per [[nfpa-70_210_branch-circuits#210.19(A)(1) General.|210.19(A)(1)]]
a receptacle branch circuit's load
is the load of the equipment intended to be served by it.
Where general-use receptacles are provided
without specific equipment in mind,
circuits will be engineered at the minimum load.
If a receptacle circuit's load is a whole multiple of 180VA
there's a good chance that's the number of devices,
or at least was at some point in the design.
## Feeders
> [!cite] NEC Article 250 (emphasis added)
> ### 250.122 Size of Equipment Grounding Conductors
> #### (A) General.
> Copper, aluminum, or copper-clad aluminum
> equipment grounding conductors of the wire type
> shall not be smaller than shown in Table 250.122,
> but in no case shall they be required to be larger
> than the circuit conductors supplying the equipment...
Apparently in the 2026 NEC First Draft Meetings,
Code Making Panel 5 clarified that the equipment grounding conductor (EGC)
never needs to be larger than the largest ungrounded conductor in any raceway
when installed in parallel.
I can not find a source to verify this.
Statements from other reputable sources including Mike Holt
are in contradiction to this idea.
***
Given a minimum ampacity, find all valid configurations.
> [!cite] NEC Article 310 (emphasis added)
> #### 310.10(H) Conductors in Parallel.
> ##### (1) General.
> Aluminum, copper-clad aluminum, or copper conductors,
> for each phase, polarity, neutral, or grounded circuit
> shall be permitted to be connected in parallel
> (electrically joined at both ends)
> _only in sizes 1/0 AWG and larger_
> where installed in accordance with 310.10(H)(2) through (H)(6).
Rank by total cost of install.
### Complexity to Ignore
#### Conductor Material
Tinned copper and copper-clad aluminum conductors
can be assumed out of scope.
### Complexity to Respect
#### Equipment Grounding Conductor Material
Wire and EGC conductors are usually assumed to match,
but it is sometimes necessary to use a copper EGC with aluminum wires,
either for spec requirements or conduit fill considerations.
## Voltage Drop
$$
V_d = I \times R \times L \times M
$$
where
* $V_d$ = Voltage Drop in volts ($V$)
* $I$ = Current in Amperes ($A$)
* $R$ = Feeder linear resistance in ohms per foot ($VA^{-1}\text{ft}^{-1}$)
* $L$ = Length of wire one way in feet ($\text{ft}$)
* $M$ = Multiplier
* $2$ for 1-phase
* $\sqrt{3}$ for 3-phase
It is often more useful to know the maximum length
a certain wiring configuration is suitable for.
$$
L = \frac{ V_d }{ I \times M } \times \frac{1}{R}
$$
* $L$ = Max length of wire one way in feet ($\text{ft}$)
* $\frac{ V_d }{ I \times M }$ = Max circuit resistance in ohms ($VA^{-1}$)
> [!info] Ohm's Law
>
> $$
> V = I \times R, \quad R = \frac{ V }{ I }, \quad I = \frac{ V }{ R }
> $$
> [!important]
> "Current" is not the OCPD rating,
> but the actual load.
## Transformers
$$
I = \frac{S}{ \sqrt{3} \times V \times E }
$$
* $I$ = nameplate current rating
* $S$ = nameplate kVA rating
* $V$ = feeder voltage
* $E$ = efficiency
## Parallel Runs
$$
\frac{1}{R_{\text{eq}}} = \frac{1}{R_1} + \frac{1}{R_2} + \frac{1}{R_3} + \dots
$$
where $R_1 = R_n$:
$$
\begin{align*}
\frac{1}{R_{\text{eq}}} &= P \times \left(\frac{1}{R_1}\right) \\
&= \frac{P}{R_1} \\
R_{\text{eq}} &= \frac{R_1}{P}
\end{align*}
$$
where
* $P$ = Number of parallel runs