2026-02-05 10:14:01
Mechanical Connection Selection
Relevant to electrical-takeoff, sourced from Joel Jansen's OneNote Takeoff Notes "Mechanical Connections".
Ben says he has never used any PVC assembly except .../PVC - ....
NM Connections
- .../
NM CABLE ASSEMBLIES
Type III, IV, and V construction. Usually only 6 AWG and smaller; EMT is expected to be cheaper for larger sizes.
MC Connections
- .../
MC CABLE ASSEMBLIES
Type I and II construction.
[!quote] Paraphrased from Source Usually only short runs, otherwise use PVC if possible.
Important
Note that MC cable may be forbidden for this application.
[!quote] Hampton Roads Navy UH - Newport News, Project Specifications MC cable shall not be allowed for wiring to mechanical equipment except for within the dwelling units.
EMT Connections
- .../
EMT SS - ... - .../
EMT COMP - ...
May be preferred for equipment in the same electrical room as the panel feeding it, otherwise treat as last resort, preferring MC or PVC.
PVC Connections
- .../
PVC - ...
Use where equipment disconnect is not integral.
- .../
PVC - ... - PVC CEILING BOX
J-box in the ceiling for mechanical connections, or where a motor-rated switch is shown.
- .../
PVC - ... - STL BOX & EXT RING
Use for equipment powered from a wall mount j-box
- .../
PVC - ... - EMT DROP
Assembly Note: Does not include j-box
Use in lieu of .../PVC - ...
where drop would be exposed
if PVC is not permitted to be exposed.
Also use for J-Boxes for Heaters.
[!example] directional unit heater shown with connection to a flush wall mount j-box
- .../
PVC - ... - EMT RISE
Assembly Note: Does not include j-box
Use if panels are located on level below panel. EMT covers vertical transition for exposed conduit
-
.../
PVC - MECH CONNECTION - SGL REC -
.../
PVC - STL BOX W/ EXT RING & COVER
For garage heaters, no labor/power term