title: Fire Alarm Takeoff
tags:
- occupational/takeoff
- status/draft
- type/guide
up: "[[takeoff-scripts]]"
aliases:
- fire alarm takeoff
---
# Fire Alarm Takeoff
> [!important]
> Complete [[conest-emergency-systems-research]] before beginning takeoff.
> [!info]
> This note is intended for practice specific to [[pdi-estimating]].
> See [[fire-alarm]] for information about fire alarm systems.
> [!info] Breakdowns
> * `System` = "FA - Fire Alarm"
## Assembly Selection
Free Air < PVC in Slab < EMT
* _High Rise (Steel & slab):_ Free air in Units, use conduit elsewhere.[^1]
* _Mid Rise, High Density (Wood frame):_ Free air, conduit only where required.
[^1]: [[2026-02-26_10-06-19]]
## Backbone
Include [[sleeving-takeoff]] as necessary.
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/...
### Fire Command Center
1. * `Area` = As shown.
* `Phase` = As shown.
.../`HEAD END EQUIP`/`... HEAD END`
### Generator Room
1. * `Area` = Same as FACR.
* `Phase` = Same as FACR.
.../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`GENERATOR ROOM ...`
### Fire Pump Room
1. * `Area` = Same as FACR.
* `Phase` = Same as FACR.
.../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FIRE PUMP ROOM ...`
### Elevator Control Rooms
> Also "Elevator Machine Room (EMR)"
> [!info] Breakdowns
> * `Area` = Same as FACR.
> * `Phase` = Same as FACR.
For each Elevator Control Room (ECR):
1. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...`
* **Count** = 1
2. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...`
* **Length** = Length measured from the most distant points of the FACR and ECR.
* Input adder length to reach the level of the ECR (Minimum 15ft).
### Elevator Shafts
> [!info] Breakdowns
> * `Area` = Same as FACR.
> * `Phase` = Same as FACR.
For each elevator shaft:
1. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV SHAFT ...`
* **Count** = 1
2. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV SHAFT ...`
* **Length** = Length measured from the most distant points of the FACR and elevator shaft.
* Input adder length to reach the level of the shaft (Minimum 15ft).
> [!important] Counting Elevator Shafts
> Adjacent elevators may be in the same or parallel shafts.
> Count the shafts accordingly:
>
> ```none
> +-----------------------------+--------------------------------+
> | | |
> | || +--------+ +--------+ || | || +--------+ || +--------+ || |
> | || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || |
> | || +--------+ +--------+ || | || +--------+ || +--------+ || |
> | ||=======================|| | ||============||============|| |
> | 1 shaft | 2 shafts |
> +-----------------------------+--------------------------------+
> ```
### FACR to Stairwells
> [!info]
> This is for the Flow/Tamper modules in the stairwells
For each stairwell:
1. * `Area` = Same as FACR.
* `Phase` = Same as FACR.
.../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO STAIRWELLS 1" CONDUIT ...`
* **Length** = Length measured from the most distant points of the FACR and stairwell.
* Input adder length to reach the level of the stairwell (Minimum 15ft).
## Terminal Cabinets
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`TERMINAL CABINET`/`ACE D ACCESSORY CABINET ENCLOSURE ...`
* _Garden Style, High Density:_ (2) 1"C
* _High Rise:_ (2) 2"C
1. Horizontal:
* `Area` = Same as FACR.
`... HORIZONTAL RUN`
* **Length** = Length measured from FACR to all electrical rooms
2. Vertical:
* `Area` = "Typical - Building All Levels"
`... RISER`
* **Length** = 10ft
> [!important]
> [[sleeving-takeoff]]
## Annunciator Panels
> [!info] Also Known As
> * Fire Alarm Annunciator (FAA)
> * Fire Alarm Annunciator Panel (FAAP)
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`ANNUNCIATORS`/`REMOTE SERIAL ANNUNCIATOR ...`
* **Length** = Length measured from the FACR to FAA or Lobby
## Central Monitoring Loop
> [!info] Breakdowns
> * `System` = "FAR - Fire Alarm Loop"
> [!important]
> Garden Style only.
>
> Fire Alarm Control Panels from each building will send a signal to a central location.
>
> In case of an emergency,
> the fire department will go to the central fire alarm station
> and find out what the issue is.
## Devices
Takeoff should always(?) use the
`DOES NOT INCLUDE COST OF DEVICES AND CABLE` assemblies,
since we will always(?) have a fire alarm quote.
### Smoke Detectors
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INITIATING DEVICES WITH WIRE - ...`/`SMOKE DETECTOR W/ BASE - ...`
* **Count:** As shown, otherwise (1) every stairwell at every level.
### Pull Stations
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INITIATING DEVICES WITH WIRE - ...`/`PULL STATION - ...`
* **Count:** As shown, otherwise (1) every stairwell at every level and every exterior exit.
### Flow/Tamper Switches
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INITIATING DEVICES ...`/`ADDRESSABLE DUAL MONITOR MODULE - FLOW/TAMPER - ...` (No free-air)
* **Count:** As shown, otherwise (1) every stairwell at every level.
### Magnetic Door Holders
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INDICATING DEVICES WITH WIRE - ...`/`MAGNETIC DOOR HOLDER - ...`
* **Count:** As shown, otherwise (2) every set of double doors.
(Typical of elevator lobbies and corridors)
### Horns, Speakers, and Strobes
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INDICATING DEVICES WITH WIRE - ...`/`INDOOR HORN STROBE - ...`
_Design Build (method 1):_
* Count every 75 ft,
* measure with circles on Bluebeam
* or divide relevant SF area by 4415[^2]
* every elevator lobby, and
* every BOH room on the first floor and garage levels.
[^2]: $\pi(\frac{75}{2})^2 \approx 4415$
_Design Build (alternative method):_
* 15ft from end of corridor,
* then every 50ft
## Fire/Smoke Dampers (FSD's)
> [!info]
> Refers to fire, smoke, and combination fire/smoke dampers.
In [[pdi-building-types#High Rise|high-rise construction]],
usually found on every level with units.
> [!tip]
> If possible, use
> * `Area` = "Typical - Fire Smoke Dampers"
> with quantity per level as shown.
For each damper, take off both
1. * `System` = "FA - Fire Alarm"
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INITIATING DEVICES ...`/`ADDRESSABLE OUTPUT RELAY CONTROL MODULE ...`
2. * `System` = "EL - Electrical"
`COMMON ASSEMBLIES`/`MISC ASSEMBLIES`/`FSD ...`