title: Article 800 General Requirements for Communications Systems
|
|
tags:
|
|
- exclude-from-word-count
|
|
- topic/construction/electrical
|
|
- type/media/reference
|
|
up: "[[nfpa-70_national-electric-code]]"
|
|
---
|
|
# Article 800 General Requirements for Communications Systems
|
|
|
|
## Part IV. Installation Methods Within Buildings
|
|
|
|
### 800.110 Raceways, Cable Routing Assemblies, and Cable Trays.
|
|
|
|
#### 800.110(A) Types of Raceways.
|
|
|
|
Wires and cables shall be permitted to be installed in raceways that comply with either 800.110(A)(1) or (A)(2).
|
|
Medium-power network-powered broadband communications cables
|
|
shall not be permitted to be installed in raceways that comply with 800.110(A)(2).
|
|
|
|
##### 800.110(A)(1) Raceways Recognized in Chapter 3.
|
|
|
|
Wires and cables shall be permitted to be installed in any raceway included in Chapter 3.
|
|
The raceways shall be installed in accordance with the requirements of Chapter 3.
|
|
|
|
##### 800.110(A)(2) Communications Raceways.
|
|
|
|
Wires and cables shall be permitted to be installed in plenum communications raceways, riser communications raceways, and general-purpose communications raceways selected in accordance with Table 800.154(b),
|
|
listed in accordance with 800.182,
|
|
and installed in accordance with 800.113 and 362.24 through 362.56,
|
|
where the requirements applicable to [[nfpa-70_362_ent|electrical nonmetallic tubing (ENT)]] apply.
|
|
|
|
##### 800.110(A)(3) Innerduct for Communications Wires and Cables, Coaxial Cables, or Network-Powered Broadband Communications Cables.
|
|
|
|
Listed plenum communications raceways,
|
|
listed riser communications raceways,
|
|
and listed general-purpose communications raceways
|
|
selected in accordance with Table 800.154(b)
|
|
shall be permitted to be installed as innerduct
|
|
in any type of listed raceway permitted in Chapter 3.
|
|
|
|
#### 800.110(B) Raceway Fill.
|
|
|
|
The raceway fill requirements of Chapters 3 and 9
|
|
shall apply to medium-power network-powered broadband communications cables.
|
|
|
|
#### 800.110(C) Cable Routing Assemblies.
|
|
|
|
Cables shall be permitted to be installed in plenum cable routing assemblies,
|
|
riser cable routing assemblies,
|
|
and general-purpose cable routing assemblies
|
|
selected in accordance with Table 800.154(c),
|
|
listed in accordance with 800.182,
|
|
and installed in accordance with 800.110(C)(1) and (C)(2) and 800.113.
|
|
|
|
##### 800.110(C)(1) Horizontal Support.
|
|
|
|
Cable routing assemblies shall be supported where run horizontally
|
|
at intervals not to exceed 900 mm (3 ft) and at each end or joint,
|
|
unless listed for other support intervals.
|
|
In no case shall the distance between supports exceed 3 m (10 ft).
|