# Subfeeds Takeoff
|
|
|
|
Use adders appropriate for the difference in elevation.
|
|
Use an additional 10ft for makeup when using cable.
|
|
|
|
> [!tip]
|
|
> Identify if and where typicals can be used
|
|
|
|
## Multi-Circuit Homerun Subfeeds
|
|
|
|
Typical of hotels and dormitories.
|
|
|
|
Route from panel to center of the room.
|
|
|
|
### Wiring Method Selection
|
|
|
|
[[wiring-method-selection#Multi-Circuit Homeruns]]
|
|
|
|
### Voltage Drop
|
|
|
|
_If_ voltage drop is to be considered in takeoff,
|
|
Use the table provided in the drawings.
|
|
If no table is provided, use the following:
|
|
|
|
| Wire Size | Max Length |
|
|
| --------: | ---------: |
|
|
| #12 | 100ft |
|
|
| #10 | 200ft |
|
|
| #8 | >200ft |
|
|
|
|
## Unit Load Center Subfeeds
|
|
|
|
Route from meter center to unit load center.
|
|
|
|
#### Voltage Drop
|
|
|
|
Larger of the listed demand current
|
|
and 80% of the panel rating.
|
|
|
|
#### Pigtail Adaptors
|
|
|
|
[[distribution-equipment#Pigtail Adaptors|Pigtail Adaptors]]
|
|
|
|
Use where conductors are oversized
|
|
(for voltage drop or otherwise).
|
|
|
|
| Load Center Size | Max Feeder Size |
|
|
| ---------------- | --------------- |
|
|
| 100A | 2/0 AWG |
|
|
| 125A | 3/0 AWG |
|
|
| 150A | 4/0 AWG |
|
|
| 225A | 300 kcmil |
|
|
| 400A | 500 kcmil |
|
|
|
|
`ITEM DATABASE`/`WIRE & CABLE ACCESSORIES`/`WIRE LUGS & SPLICING`/`PIGTAIL ADAPTORS...`/`ADAPTOR STRAIGHT PIGTAIL - ...`
|
|
|
|
#### Meter Center Troughs
|
|
|
|
Only for PVC subfeeds where we own voltage drop.
|
|
|
|
* `Area` = "Typical - Building Levels With Meter Centers"
|
|
* `System` = "Electrical"
|
|
* `Phase` = "Sub Feeders"
|
|
|
|
`ITEM DATABASE`/`DISTRIBUTION`/`BUDGET ITEMS $ & LBR`/`METER CENTER WIRE TROUGH ($400/E)`
|