# Feeder Sizing
|
|
|
|
> [!cite] 250.122 Size of Equipment Grounding Conductors
|
|
> **(A) General.** Copper, aluminum, or copper-clad aluminum
|
|
> equipment grounding conductors of the wire type
|
|
> shall not be smaller than shown in Table 250.122,
|
|
> but in no case shall they be required to be larger
|
|
> than the circuit conductors supplying the equipment...
|
|
|
|
Apparently in the 2026 NEC First Draft Meetings,
|
|
Code Making Panel 5 clarified that the equipment grounding conductor (EGC)
|
|
never needs to be larger than the largest ungrounded conductor in any raceway
|
|
when installed in parallel.
|
|
I can not find a source to verify this.
|
|
Statements from other reputable sources including Mike Holt
|
|
are in contradiction to this idea.
|
|
|
|
***
|
|
|
|
Given a minimum ampacity, find all valid configurations.
|
|
|
|
> [!cite] 310.10(H) Conductors in Parallel.
|
|
> **(1) General.** Aluminum, copper-clad aluminum, or copper conductors,
|
|
> for each phase, polarity, neutral, or grounded circuit
|
|
> shall be permitted to be connected in parallel
|
|
> (electrically joined at both ends)
|
|
> *only in sizes 1/0 AWG and larger*
|
|
> where installed in accordance with 310.10(H)(2) through (H)(6).
|
|
|
|
Rank by total cost of install.
|
|
|
|
## Complexity to Ignore
|
|
|
|
### Conductor Material
|
|
|
|
Tinned copper and copper-clad aluminum conductors
|
|
can be assumed out of scope.
|
|
|
|
## Complexity to Respect
|
|
|
|
Wire and EGC conductors are usually assumed to match,
|
|
but it is sometimes preferable to use a copper EGC
|
|
with high-amp aluminum parallel feeds. |