Minimum Wire Size for Small Garage Buildings

Relevant to electrical-takeoff and fixtures-takeoff:

hilltop-gardens has 3 separate garage buildings, each with 12 isolated bays. The buildings are about 70ft long, with all runs less than 100ft.

I asked joel-jansen if it would be necessary to use minimum 10 AWG as is conest standard for pdi-breakdowns#Bid Item Garage. He said it would not be, and confirmed 12 AWG is acceptable in this case.