id:
aliases: []
tags:
- topic/electrical
- type/encyclopedia
---
# Raceway Terms
## "Raceway"
> [!quote] NEC Article 100
> **Raceway.**
> An enclosed channel
> designed expressly for holding wires, cables, or busbars,
> with additional functions as permitted in this _Code_. (CMP-8)
### "Duct"
> [!quote] NEC 310.2 Definitions
> **Electrical Ducts.**
> Electrical conduits, or other raceways round in cross section,
> that are suitable for use underground or embedded in concrete.
> [!info] Duct Bank
> "Duct bank" is not given explicit definition in the NEC,
> however it is used frequently to refer to any group of ducts,
> _even as few as one_, as shown in Figure 310.60(C)(3).
> It is always spelled as two words.
## "Wiring Method"
"Wiring method" is not given explicit definition in the NEC.
> [!quote] NEC 110.8 Wiring Methods
> Only wiring methods recognized as suitable are included in this Code.
> The recognized methods of wiring
> shall be permitted to be installed in any type of building or occupancy,
> except as otherwise provided in this Code.
> [!quote] NEC 300.1(A) All Wiring Installations
> This article covers general requirements
> for wiring methods and materials
> for all _wiring installations_ (emphasis added)
> unless modified by other articles in Chapter 3.
Nor is wiring installation, however by closest definition
it can be assumed premises wiring includes all wiring installations.
> [!quote] NEC Article 100
> **Premises Wiring (System).**
> Interior and exterior wiring,
> including power, lighting, control, and signal circuit wiring
> together with all their associated hardware, fittings, and wiring devices,
> both permanently and temporarily installed.
> This includes
> (a) wiring from the service point or power source to the outlets or
> (b) wiring from and including the power source to the outlets where there is no service point.
Notably, Chapter 3 does not prescribe requirements for _raceway_, but for _wiring installations_.
As such, conduit used for other purposes (e.g. routing beverage tubing) is out of scope.
Raceways used for supporting communications cables _would be_ out of scope,
except for Article 800.110:
> [!quote] NEC 800.110(A)(1) Raceways Recognized in Chapter 3
> Communications wires and cables shall be permitted
> to be installed in any raceway included in Chapter 3.
> The raceways shall be installed in accordance
> with the requirements of Chapter 3.
Raceway is not a wiring method unless it is used to support premises wiring,
which communications cabling is not.
It is not appropriate to say "EMT conduit is a wiring method"
(granted the NEC does use this syntax occasionally),
because a recognized wiring method must include
the wiring, splices, pull boxes, outlet boxes, and supports
necessary of a complete wiring installation,
each of which has countless options.
It may be appropriate to refer to "MC cable" as a wiring method
if you and your audience understand the name as shorthand
for a more specific, standard framework.
## Takeaways
No part of a manufactured cable assembly (e.g. MC cable)
can be considered a raceway.
It is usually incorrect to refer to wiring methods
in the singular (e.g. installed in _a_ wiring method).