# Medium Voltage
"Medium voltage" refers to voltage systems greater than 600V.
## Insulation Level
> [!example]
>
> > [!cite] 343 Madison Avenue Project Specifications, emphasis added
> > 2.2 MEDIUM VOLTAGE CABLES (CON EDISON)
> > * ...
> > * H. Construction
> > * ...
> > * 3. Insulation
> > * ...
> > * c. _The minimum average insulation thickness shall be not less than 175 mils._
> > The minimum thickness at any cross-section of the insulation
> > shall be not less than 90% of the specified minimum average thickness.
>
> In this case 100% insulation level is appropriate for 15kV conductors.
[[nfpa-70_311_mv-conductors#311.10(B) Thickness of Insulation and Jacket for Nonshielded Insulated Conductors.]]
| Voltage Rating | Insulation Level | Insulation Thickness |
| --------------:| ----------------:| --------------------:|
| 5kV | 100% | 90 mils |
| 5kV | 133% | 115 mils |
| 5kV | 173% | 140 mils |
| 8kV | 100% | 115 mils |
| 8kV | 133% | 140 mils |
| 8kV | 173% | 175 mils |
| 15kV | 100% | 175 mils |
| 15kV | 133% | 220 mils |
| 15kV | 173% | 260 mils |
| 25kV | 100% | 260 mils |
| 25kV | 133% | 320 mils |
| 25kV | 173% | 420 mils |
| 35kV | 100% | 345 mils |
| 35kV | 133% | 420 mils |
| 35kV | 173% | 580 mils |