# Fire Alarm
|
|
|
|
> [!info]
|
|
> See [[fire-alarm]] for information about fire alarm systems.
|
|
|
|
## Backbone
|
|
|
|
Put all backbone takeoff in the `Area` of the Fire Command Center.
|
|
Include [[sleeving-takeoff]] as necessary.
|
|
|
|
### Fire Command Center
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`HEAD END EQUIP`/`... HEAD END`
|
|
|
|
### Generator Room
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`GENERATOR ROOM ...`
|
|
|
|
### Fire Pump Room
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FIRE PUMP ROOM ...`
|
|
|
|
### FACR to Elevator Shafts
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV SHAFT ...`
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV SHAFT ...`
|
|
|
|
Measure Length from the most distant points of the FACR and each shaft.
|
|
Input adder length to reach the bottom of the pit (Minimum 15ft).
|
|
|
|
> [!important] Counting Elevator Shafts
|
|
> Adjacent elevators may be in the same or parallel shafts.
|
|
> Count the shafts accordingly:
|
|
>
|
|
> ```
|
|
> | 1 shaft | 2 shafts |
|
|
> | || +--------+ +--------+ || | || +--------+ || +--------+ || |
|
|
> | || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || |
|
|
> | || +--------+ +--------+ || | || +--------+ || +--------+ || |
|
|
> | ||=======================|| | ||============||============|| |
|
|
> | | |
|
|
> ```
|
|
|
|
### FACR to Elevator Control Rooms
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...`
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...`
|
|
|
|
* Measure the Horizontal and Vertical Distance from the FACR to the ECR.
|
|
* Use Typicals for the vertical riser. (10ft per floor)
|
|
|
|
### FACR to Stairwells
|
|
|
|
> [!info]
|
|
> This is for the Flow/Tamper modules in the stairwells
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO STAIRWELLS ...`
|
|
|
|
* Measure from the furthest end of FACR to the furthest end of the stairwell to find length
|
|
|
|
### Terminal Cabinets
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`TERMINAL CABINET`/`ACE D ACCESSORY CABINET ENCLOSURE (2) 2" ...`
|
|
|
|
* _Garden Style, High Density:_ (2) 1"C
|
|
* _High Rise:_ (2) 2"C
|
|
|
|
Horizontal:
|
|
* Measure from the Fire Command room to all electrical rooms
|
|
|
|
Vertical:
|
|
* Use 10ft Riser in Typical
|
|
* Add [[sleeving-takeoff]] as necessary.
|
|
|
|
### Annunciator Panels
|
|
|
|
> [!info] Also Known As
|
|
> * Fire Alarm Annunciator (FAA)
|
|
> * Fire Alarm Annunciator Panel (FAAP)
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`ANNUNCIATORS`/`REMOTE SERIAL ANNUNCIATOR ...`
|
|
|
|
* Measure from the Fire Command Room to FAA or Lobby
|
|
|
|
## Devices
|
|
|
|
### Smoke Detectors
|
|
|
|
_Design Build:_
|
|
Count every stairwell at every level.
|
|
|
|
### Pull Stations
|
|
|
|
_Design Build:_
|
|
Count every stairwell at every level
|
|
and every exterior exit.
|
|
|
|
### Flow/Tamper Switches
|
|
|
|
No free air. if wood frame, take off as EMT.
|
|
|
|
_Design Build:_
|
|
Count every stairwell at every level.
|
|
|
|
### Magnetic Door Holders
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INDICATING DEVICES WITH WIRE - ...`/`MAGNETIC DOOR HOLDER - ...`
|
|
|
|
_Design Build:_
|
|
Count every set of double doors.
|
|
(Typical of elevator lobbies and corridors)
|
|
|
|
### Speaker Strobes
|
|
|
|
_Design Build:_
|
|
* Count every 75 ft,
|
|
* measure with circles on Bluebeam
|
|
* or divide relevant SF area by 4415
|
|
* $\pi(\frac{75}{2})^2 \approx 4415$
|
|
* every elevator lobby,
|
|
* and every BOH room on the first floor and garage levels.
|
|
|
|
## Firefighter Phone System
|
|
|
|
* firefighter phone jacks
|
|
* fire warden station
|
|
* fire phone cabinet
|
|
|
|
Communicates directly with FACR.
|
|
Not related to responder radio.
|
|
|
|
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`COMMUNICATION DEVICES ...`/`...`
|
|
|
|
## Fire Smoke Dampers (FSD's)
|
|
|
|
For each damper, take off both
|
|
|
|
`System` = "FA - Fire Alarm"
|
|
|
|
`COMMON ASSEMBLIES`/`MISC ASSEMBLIES`/`FSD ...`
|
|
|
|
and "EL - Electrical"
|
|
|
|
`COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS (UP TO 100A)`/.../...
|