Files
zmVault/electrical-takeoff.md
T

102 lines
2.1 KiB
Markdown

---
id: electrical
aliases: []
title: Electrical Takeoff
tags:
- authorship/original
- destiny/permanent
- occupational/takeoff
- status/draft
- type/guide
---
# Electrical Takeoff
> [!important]
> Complete [[pre-takeoff-research]],
> including [[wiring-method-selection]] and [[wiring-device-research]],
> before beginning takeoff.
> [!tip]
> Use [[heating-designations]] for uncertain scope.
## Garage
In conventional slab garages,
use ENT and PVC as permitted.
In precast slab garages, use EMT.
## Receptacles
## Floor Boxes
`COMMON ASSEMBLIES`/`FLOOR BOXES`/...
### Poke-Thru's
Use suitable floor box assembly,
delete floor box items,
add `ITEM DATABASE`/`WIRING & SYSTEM DEVICES`/`FLOOR BOXES & FITTTINGS`/`GENERIC - FLOOR BOXES & ACCESS`/`POKE-THRU W/ DUPLEX RECEPTACLE`
## Homeruns
### Lighting
* `Area` = "XX - Level XX Building"
* `Phase` = "Building - Back of House (BOH)"
Takeoff homeruns in Building breakdowns,
even where serving Amenity spaces.
## Mechanical Connections
`COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS ...`/...
### Stair Pressurization Fans
Assume branch circuit conductors must be protected
per [[fire-resistive-wiring-methods-takeoff]].
### Roof Mounted Equipment
#### Unit Condensing Units
Put homeruns on the `Area` of the dwelling unit.
Put connections on the `Area` of the CU.
.../`CONDENSOR HOME RUNS`
.../`CU CONDENSER SLEEVE W/ FLEX - NO HMRN WIRE`
`NO SLEEVE`:
Routed through a "doghouse"
(a large weatherproof opening)
with several other feeds.
Used where drilling openings for individual sleeves
would be impractical.
`PVC SLEEVE`, `EMT SLEEVE`:
Routed up through the roof,
(optionally through a disconnect)
with flex to the equipment.
#### Equipment Racks
Max 20 disconnects per rack
`DISTRIBUTIION`/`TRAPEZE RACK SUPPORT ...`/`...`
### Trash Chute
1. **Horizontal:**
`COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS ...`/...
* **Length** = Length per drawings, 100ft if not shown.
2. **Vertical (Riser):**
* `Area` = "Typical - Building All Levels"
Takeoff: `COMMON ASSEMBLIES`/`MISC ASSEMBLIES`/`TRASH CHUTE RISER CIRCUIT...`
* Length = average floor to floor height