# Fire Resistive Wiring Methods
|
|
|
|
## Requirements
|
|
|
|
Permitted methods for fire protection of emergency feeders
|
|
are specified in [[nfpa-70_700_emergency-systems#700.10(D)(2) Feeder-Circuit Wiring.|700.10(D)(2)]].
|
|
|
|
![[nfpa-70_700_emergency-systems#700.10(D)(2) Feeder-Circuit Wiring.]]
|
|
|
|
the requirements of which only apply to occupancies listed in
|
|
[[nfpa-70_700_emergency-systems#700.10(D)(1) Occupancies.|700.10(D)(1)]]
|
|
|
|
![[nfpa-70_700_emergency-systems#700.10(D)(1) Occupancies.]]
|
|
|
|
Note that even in these occupancies only [[nfpa-70_100_definitions#Feeder.|feeders]]
|
|
require fire protection, not [[nfpa-70_100_definitions#Branch Circuit.|branch circuits]].
|
|
|
|
## Construction
|
|
|
|
> [!info] Keywords
|
|
> * Low Smoke Zero Halogen (LSZH)
|
|
|
|
### Fire Resistive Metal-Clad (MC) Cable
|
|
|
|
[[nfpa-70_330_mc-cable|330 Metal-Clad Cable: Type MC]]
|
|
|
|
### Mineral Insulated (MI) Cable
|
|
|
|
[[nfpa-70_332_mi-cable|332 Mineral-Insulated, Metal-Sheathed Cable: Type MI]]
|
|
|
|
When terminating single conductors in a ferrous metal enclosure,
|
|
it is necessary to terminate MI cables in a brass plate
|
|
to prevent heating due to ferroelectric hysteresis
|
|
Cut out and replace a section of the enclosure with the plate
|
|
|
|
When cutting a hole in the enclosure would void its listing,
|
|
or is otherwise not allowed,
|
|
the cables can be terminated through a brass plate into a junction box
|
|
and power brought to the enclosure through a conventional raceway.
|
|
|
|
> [!info]
|
|
> According to Pyrotenax literature,
|
|
> the intermediate junction box method is obligatory
|
|
> for fire pump controllers.
|
|
|
|
### Fire Resistive Cable-in-Conduit (CIC)
|
|
|
|
### Notes
|
|
|
|
> [!info] "Vitalink" vs "Lifeline" cable ^vitalink-vs-lifeline
|
|
> VITALink® and Lifeline® are brand names
|
|
> (of Omni Cable and Prysmian Group respectively),
|
|
> not cable types.
|
|
> _Both_ brands include MC _and_ CIC cables.
|
|
|
|