# Raceway Terms
|
|
|
|
## "Raceway"
|
|
|
|
![[nfpa-70_100_definitions#Raceway.]]
|
|
|
|
### "Duct"
|
|
|
|
> [!quote] NEC 310.2 Definitions
|
|
> **Electrical Ducts.**
|
|
> Electrical conduits, or other raceways round in cross section,
|
|
> that are suitable for use underground or embedded in concrete.
|
|
|
|
> [!info] Duct Bank
|
|
> "Duct bank" is not given explicit definition in the NEC,
|
|
> however it is used frequently to refer to any group of **ducts**,
|
|
> _even as few as one_, as shown in Figure 310.60(C)(3).
|
|
> ==It is always spelled as two words.==
|
|
|
|
## "Wiring Method"
|
|
|
|
"Wiring method" is not given explicit definition in the NEC.
|
|
|
|
![[nfpa-70_110_requirements#110.8 Wiring Methods]]
|
|
|
|
![[nfpa-70_300_general-requirements#300.1(A) All Wiring Installations.]]
|
|
|
|
Nor is wiring installation,
|
|
however by closest definition
|
|
it can be assumed **premises wiring**
|
|
includes all wiring installations.
|
|
|
|
![[nfpa-70_100_definitions#Premises Wiring (System).]]
|
|
|
|
### Inappropriate Use
|
|
|
|
Notably, Chapter 3 does not prescribe requirements for _raceway_,
|
|
but for _wiring installations_.
|
|
As such, conduit used for other purposes
|
|
(e.g. routing beverage tubing) is out of scope.
|
|
|
|
Raceways used for supporting communications cables
|
|
_would be_ out of scope, except for Article 800.110:
|
|
|
|
> [!quote] [[nfpa-70_800#800.110(A)(1) Raceways Recognized in Chapter 3.]]
|
|
> Communications wires and cables shall be permitted
|
|
> to be installed in any raceway included in Chapter 3.
|
|
> _The raceways shall be installed in accordance_
|
|
> _with the requirements of Chapter 3._
|
|
|
|
Raceway is not a _wiring method_
|
|
unless it is used to support _premises wiring_,
|
|
which communications cabling is not.
|
|
|
|
It is not appropriate to say "EMT conduit is _a_ wiring method"
|
|
(granted the NEC does use similar phrasing occasionally),
|
|
because any recognized wiring method must include the
|
|
* wiring,
|
|
* splices,
|
|
* pull boxes,
|
|
* outlet boxes,
|
|
* and supports
|
|
necessary of a complete wiring installation,
|
|
each of which has countless options.
|
|
|
|
It may be more consistent with NEC phrasing
|
|
to say that each component is _a_ wiring method,
|
|
but this is less consistent with common use.
|
|
|
|
### Appropriate Use
|
|
|
|
It may be appropriate to refer to "MC cable" as _a_ wiring method
|
|
if you and your audience understand the name as shorthand
|
|
for a more specific, standard framework.
|
|
|
|
In a robustly implemented specification-based takeoff software,
|
|
an assembly's specifications would describe its wiring methods.
|
|
A 20A and 30A branch circuit may utilize identical "wiring methods".
|
|
|
|
## Takeaways
|
|
|
|
No part of a manufactured cable assembly (e.g. MC cable)
|
|
can be considered a raceway.
|
|
|
|
It is usually incorrect to refer to wiring methods
|
|
in the singular (e.g. installed in _a_ wiring method).
|