# Lighting Controls
|
||
|
||
## Technologies
|
||
|
||
* Triac (Line voltage dim)
|
||
* Analog (0-10V dim)
|
||
* Digital
|
||
* Wireless
|
||
|
||
All these control methods are likely to appear in drawings.
|
||
|
||
### 0-10V Dimming
|
||
|
||
In conduit:
|
||
|
||
```
|
||
Southwire 64350501
|
||
SIMpull® 16/2 Low Voltage Signal Cable, Blue
|
||
```
|
||
|
||
This method is compliant with NEC 725.136(I)(1),
|
||
which allows control circuits to share a raceway with power conductors
|
||
if either all of the power conductors or all of the control conductors
|
||
are themselves in a raceway,
|
||
or in metal-sheathed, metal-clad, non–metallic-sheathed, or Type UF cable.
|