## Equipment Grounding Conductor Sizing
|
||||
|
||||
[[virginia-live-casino-and-hotel]]
|
||||
one-lines specify ~~a feeder~~ as
|
||||
`(6) SETS OF: 4#600, 1#450G, 4"C.`
|
||||
|
||||
The use of 450kcmil for the EGC is strange:
|
||||
|
||||
* It is not a size specified by
|
||||
[[nfpa-70_250_grounding#Table 250.122 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment|Table 250.122]]
|
||||
|
||||
* it is a non-standard size anyway,
|
||||
not appearing in [[nfpa-70_ch09|Chapter 9]] tables,
|
||||
the [[neca-mlu]],
|
||||
or our Accubid database.
|
||||