Distributed Antenna Systems (DAS) Takeoff

Distributed Antenna Systems (DAS) Takeoff

Important

Complete emergency-systems-research before beginning takeoff.

[!info] See emergency-communications-systems for information about Emergency Responder Radio Communication Systems (ERRCS).

[!info] Cellular Systems Less common than ERRCS are "cellular DAS" systems

Backbone

FACR to Every Elev. Shaft

COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/DAS ASSEMBLIES/FACR TO ELEV PIT = ...

Match Fire Alarm takeoff Length and Count

FACR to Every Staircase

COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/DAS ASSEMBLIES/FACR TO STAIRWELL = ...

Match Fire Alarm takeoff Length and Count

Stairwell Riser Every 2 Floors

COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/DAS ASSEMBLIES/STAIRWELL RISER EVERY 2 FLRS = 1 1/2" EMT (20') W/ 16X16X6 BOX

Create a Stairwell typical on every other floor

FACR to Electric Room

COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/DAS ASSEMBLIES/FACR TO 2HR-RATED RM = 2" PVC40

Match Fire Alarm takeoff Length

Electric Room Riser to Every Floor

COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/DAS ASSEMBLIES/2HR-RATED RM RISER TO EVERY FLR = 2" EMT (15') W/ 16X16X6 BOX

Takeoff in every Electric Room

Top 2H Rated Room To Roof

COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/DAS ASSEMBLIES/TOP 2HR RATED RM TO ROOF = 2" EMT W/ RMC WEATHERHEAD & IMC STUB

Use 15' or Height of ceiling on last building level

Horizontal

CORRIDORS EMT OH = 1 1/2" EMT W/ 16X16X6 BOX EVERY 80' CA.28.31.23

CORRIDORS DECK = 1 1/2" PVC40, STUBBY, FLEX W/ 16X16X6 BOX EVERY 80' CA.28.31.21

1-1/2 through corridors w/ 16x16x6 J-Box