Files
zmVault/distributed-antenna-systems-takeoff.md
T

74 lines
1.9 KiB
Markdown

---
id:
aliases:
- das
tags:
- authorship/original
- destiny/permanent
- occupational/takeoff/standalone-systems
- status/draft
- type/guide
title: Distributed Antenna Systems (DAS) Takeoff
---
# Distributed Antenna Systems (DAS) Takeoff
> [!important]
> Complete [[emergency-systems-research]] before beginning takeoff.
> [!info]
> See [[emergency-communications-systems]] for information
> about Emergency Responder Radio Communication Systems (ERRCS).
> [!info] Cellular Systems
> Less common than ERRCS are "cellular DAS" systems
## Backbone
### FACR to Every Elev. Shaft
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO ELEV PIT = ...`
Match Fire Alarm takeoff Length and Count
### FACR to Every Staircase
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO STAIRWELL = ...`
Match Fire Alarm takeoff Length and Count
### Stairwell Riser Every 2 Floors
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`STAIRWELL RISER EVERY 2 FLRS = 1 1/2" EMT (20') W/ 16X16X6 BOX`
Create a Stairwell typical on every other floor
### FACR to Electric Room
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO 2HR-RATED RM = 2" PVC40`
Match Fire Alarm takeoff Length
### Electric Room Riser to Every Floor
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`2HR-RATED RM RISER TO EVERY FLR = 2" EMT (15') W/ 16X16X6 BOX`
Takeoff in every Electric Room
### Top 2H Rated Room To Roof
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`TOP 2HR RATED RM TO ROOF = 2" EMT W/ RMC WEATHERHEAD & IMC STUB`
Use 15' or Height of ceiling on last building level
## Horizontal
CORRIDORS EMT OH = 1 1/2" EMT W/ 16X16X6 BOX EVERY 80'
CA.28.31.23
CORRIDORS DECK = 1 1/2" PVC40, STUBBY, FLEX W/ 16X16X6 BOX EVERY 80'
CA.28.31.21
1-1/2 through corridors w/ 16x16x6 J-Box
Length for every corridor/garage