title: Article 220 Branch-Circuit, Feeder, and Service Load Calculations
|
||
---
|
||
# Article 220 Branch-Circuit, Feeder, and Service Load Calculations
|
||
|
||
## Part I. General
|
||
|
||
### 220.1 Scope.
|
||
|
||
This article provides requirements
|
||
for calculating branch-circuit, feeder, and service loads.
|
||
Part I provides general requirements for calculation methods.
|
||
Part II provides calculation methods for branch-circuit loads.
|
||
Parts III and IV provide calculation methods for feeder and service loads.
|
||
Part V provides calculation methods for farm loads.
|
||
|
||
Informational Note No. 1:
|
||
See examples in Informative Annex D.
|
||
|
||
Informational Note No. 2:
|
||
See Figure 220.1 for information on the organization of Article 220.
|
||
|
||
### Figure 220.1 Branch-Circuit, Feeder, and Service Load Calculation Methods.
|
||
|
||
<!-- TODO: FIGURE OMITTED -->
|
||
|
||
<!-- TODO: TEXT OMITTED -->
|
||
|
||
### 220.14 Other Loads -- All Occupancies.
|
||
|
||
In all occupancies, the minimum load for each outlet
|
||
for general-use receptacles and outlets not used for general illumination
|
||
shall not be less than that calculated in 220.14(A) through (M),
|
||
the loads shown being based on nominal branch-circuit voltages.
|
||
|
||
Exception:
|
||
The loads of outlets serving switchboards and switching frames in telephone exchanges
|
||
shall be waived from the calculations.
|
||
|
||
<!-- TODO: TEXT OMITTED -->
|
||
|
||
#### 220.14(A) Specific Appliances or Loads.
|
||
|
||
An outlet for a specific appliance
|
||
or other load not covered in 220.14(B) through (M)
|
||
shall be calculated based on the ampere rating
|
||
of the appliance or load served.
|
||
|
||
#### 220.14(B) Electric Dryers and Electric Cooking Appliances in Dwellings and Household Cooking Appliances Used in Instructional Programs.
|
||
|
||
Load calculations shall be permitted
|
||
as specified in 220.54 for electric dryers
|
||
and in 220.55 for electric ranges and other cooking appliances.
|
||
|
||
#### 220.14(C) Motor Outlets.
|
||
|
||
Loads for motor outlets shall be calculated
|
||
in accordance with the requirements in 430.22, 430.24, and 440.6.
|
||
|
||
#### 220.14(D) Luminaires.
|
||
|
||
An outlet supplying luminaire(s) shall be calculated
|
||
based on the maximum volt-ampere rating of the equipment
|
||
and lamps for which the luminaire(s) is rated.
|
||
|
||
#### 220.14(E) Heavy-Duty Lampholders.
|
||
|
||
Outlets for heavy-duty lampholders
|
||
shall be calculated at a minimum of 600 volt-amperes.
|
||
|
||
#### 220.14(F) Sign and Outline Lighting.
|
||
|
||
Sign and outline lighting outlets
|
||
shall be calculated at a minimum of 1200 volt-amperes
|
||
for each required branch circuit specified in 600.5(A).
|
||
|
||
#### 220.14(G) Show Windows.
|
||
|
||
Show windows shall be calculated
|
||
in accordance with either of the following:
|
||
|
||
* (1) The unit load per outlet as required in other provisions of this section
|
||
* (2) At 200 volt-amperes per linear 300 mm (1 ft) of show window
|
||
|
||
#### 220.14(H) Fixed Multioutlet Assemblies.
|
||
|
||
Fixed multioutlet assemblies used in other than dwelling units
|
||
or the guest rooms or guest suites of hotels or motels
|
||
shall be calculated in accordance with (H)(1) or (H)(2).
|
||
For the purposes of this section,
|
||
the calculation shall be permitted
|
||
to be based on the portion that contains receptacle outlets.
|
||
|
||
* (1) Where appliances are unlikely to be used simultaneously,
|
||
each 1.5 m (5 ft) or fraction thereof
|
||
of each separate and continuous length
|
||
shall be considered as one outlet of not less than 180 volt-amperes.
|
||
|
||
* (2) Where appliances are likely to be used simultaneously,
|
||
each 300 mm (1 ft) or fraction thereof
|
||
shall be considered as an outlet of not less than 180 volt-amperes.
|
||
|
||
#### 220.14(I) Receptacle Outlets.
|
||
|
||
Except as covered in 220.14(J) and (K),
|
||
receptacle outlets shall be calculated at not less than 180 volt-amperes
|
||
for each single or for each multiple receptacle on one yoke.
|
||
A single piece of equipment consisting of a multiple receptacle
|
||
comprised of four or more receptacles
|
||
shall be calculated at not less than 90 volt-amperes per receptacle.
|
||
This provision shall not be applicable to the receptacle outlets
|
||
specified in [[nfpa-70_210_branch-circuits#210.11(C)(1) Small-Appliance Branch Circuits.|210.11(C)(1)]]
|
||
and [[nfpa-70_210_branch-circuits#210.11(C)(2) Laundry Branch Circuits.|(C)(2)]].
|
||
|
||
#### 220.14(J) Dwelling Units.
|
||
|
||
In one-family, two-family, and multifamily dwellings,
|
||
the minimum unit load shall be not less than 33 volt-amperes/m$^2$ (3 volt-amperes/ft$^2$).
|
||
The lighting and receptacle outlets specified in 220.14(J)(1), (J)(2), and (J)(3)
|
||
are included in the minimum unit load.
|
||
No additional load calculations shall be required for such outlets.
|
||
The minimum lighting load shall be determined using the minimum unit load
|
||
and the floor area as determined in 220.11 for dwelling occupancies.
|
||
Motors rated less than 1⁄8 hp and connected to a lighting circuit
|
||
shall be considered part of the minimum lighting load.
|
||
|
||
* (1) All general-use receptacle outlets of 20-ampere rating or less,
|
||
including receptacles connected to the circuits in 210.11(C)(3) and 210.11(C)(4)
|
||
* (2) The receptacle outlets specified in 210.52(E) and (G)
|
||
* (3) The lighting outlets specified in 210.70
|
||
|
||
#### 220.14(K) Office Buildings.
|
||
|
||
In office buildings, the receptacle loads
|
||
shall be calculated to be the larger of (1) or (2):
|
||
|
||
* (1) The calculated load from 220.14(I)
|
||
after all demand factors have been applied
|
||
* (2) 11 volt-amperes/m$^2$ or 1 volt-ampere/ft$^2$
|
||
|
||
#### 220.14(L) Other Outlets.
|
||
|
||
Other outlets not covered in 220.14(A) through (K)
|
||
shall be calculated based on 180 volt-amperes per outlet.
|
||
|
||