# 2026-04-15 11:00:38
|
|
|
|
## Equipment Grounding Conductor Sizing
|
|
|
|
[[virginia-live-casino-and-hotel]]
|
|
one-lines specify ~~a feeder~~ as
|
|
`(6) SETS OF: 4#600, 1#450G, 4"C.`
|
|
|
|
The use of 450kcmil for the EGC is strange:
|
|
|
|
* It is not a size specified by
|
|
[[nfpa-70_250_grounding#Table 250.122 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment|Table 250.122]]
|
|
|
|
* it is a non-standard size anyway,
|
|
not appearing in [[nfpa-70_ch09|Chapter 9]] tables,
|
|
the [[neca-mlu]],
|
|