# Article 215 Feeders
|
|
|
|
## 215.1 Scope.
|
|
|
|
This article covers the installation requirements, overcurrent protection requirements, minimum size, and ampacity of conductors for
|
|
feeders.
|
|
|
|
Exception:
|
|
Feeders for electrolytic cells as covered in 668.3(C)(1) and (C)(4).
|
|
|
|
#### 215.2 Minimum Rating and Size.
|
|
|
|
#### 215.2(A) Feeders Not More Than 1000 Volts.
|
|
|
|
#### 215.2(A)(1) General.
|
|
|
|
Feeder conductors shall have an ampacity
|
|
not less than the larger of 215.2(A)(1)(a) or (A)(1)(b)
|
|
and shall comply with 110.14(C).
|
|
|
|
* (a) Where a feeder supplies continuous loads
|
|
or any combination of continuous and noncontinuous loads,
|
|
the minimum feeder conductor size shall have an ampacity
|
|
not less than the noncontinuous load plus 125 percent of the continuous load.
|
|
|
|
* (b) The minimum feeder conductor size
|
|
shall have an ampacity not less than the maximum load to be served
|
|
after the application of any adjustment or correction factors
|
|
in accordance with
|
|
[[nfpa-70_310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts -- 2000 Volts.|310.14]].
|
|
|
|
Exception No. 1:
|
|
If the assembly, including the overcurrent devices protecting the feeder(s),
|
|
is listed for operation at 100 percent of its rating,
|
|
the ampacity of the feeder conductors shall be permitted to be not less
|
|
than the sum of the continuous load plus the noncontinuous load.
|
|
|
|
Exception No. 2:
|
|
Where a portion of a feeder is connected at both its supply and load ends
|
|
to separately installed pressure connections as covered in 110.14(C)(2),
|
|
it shall be permitted to have an ampacity
|
|
not less than the sum of the continuous load plus the noncontinuous load.
|
|
No portion of a feeder installed under this exception
|
|
shall extend into an enclosure containing either the feeder supply
|
|
or the feeder load terminations, as covered in 110.14(C)(1).
|
|
|
|
Exception No. 3:
|
|
Grounded conductors that are not connected to an overcurrent device
|
|
shall be permitted to be sized at 100 percent
|
|
of the continuous and noncontinuous load.
|
|
|
|
Informational Note No. 1:
|
|
See Examples D1 through D11 in Informative Annex D.
|
|
|
|
Informational Note No. 2:
|
|
Conductors for feeders, as defined in Article 100,
|
|
sized to prevent a voltage drop exceeding 3 percent
|
|
at the farthest outlet of power, heating, and lighting loads,
|
|
or combinations of such loads,
|
|
and where the maximum total voltage drop on both feeders and branch circuits
|
|
to the farthest outlet does not exceed 5 percent,
|
|
will provide reasonable efficiency of operation.
|
|
|
|
Informational Note No. 3:
|
|
See 210.19(A), Informational Note No. 4, for voltage drop for branch circuits.
|
|
|
|
#### 215.2(A)(2) Grounded Conductor.
|
|
|
|
The size of the feeder circuit grounded conductor
|
|
shall not be smaller than that required by 250.122,
|
|
except that 250.122(F) shall not apply
|
|
where grounded conductors are run in parallel.
|
|
|
|
Additional minimum sizes shall be as specified in 215.2(A)(3)
|
|
under the conditions stipulated.
|