Fire Alarm
Sequence
1. Estimate preparation
- Initial the OneNote
- Read about the project specifications and construction type
- Find Fire Alarm plans (if present)
- Locate the following rooms:
- Fire Command Center (FCC)
- Generator Room
- Fire Pump Room
- Elevator Control Rooms
- Elevator Shafts
- Stairwells
2. Takeoff
Riser
Fire Command Center
{Building Type} Head End CA.30.23.X
Generator Room
CA.30.22.2
Fire Pump Room
CA.30.22.4
FACR to Elevator Shafts
Elevator Shafts (CA.30.22.8)
FACR TO ELEV SHAFT 1 ½" (CA.30.22.10/11)
Measure Length from the most distant points of the FACR and each shaft. Input adder length to reach the bottom of the pit (Minimum 15ft adder).
| 1 shaft | 2 shafts |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| ||=======================|| | ||============||============|| |
| | |
FACR to Elevator Control Rooms
Elevator Control Room (CA.30.22.6)
FACR/FCC TO ELEV CONTROL ROOM (CA.30.22.13/14)
- Measure the Horizontal and Vertical Distance from the FACR to the ECR.
- Use Typicals for the vertical riser. (Ex// 10' per floor)
FACR to Stairwells
FACR TO STAIRWELLS 1" PVC (CA.30.22.17)
-
Measure from the furthest end of FACR to the furthest end of the stairwell to find length
-
This is for the Flow/Tamper modules in the stairwells
Terminal Cabinets
TERMINAL CABINETS (2) 2" EMT/PVC (CA.30.26.X)
Horizontal:
- Measure from the Fire Command room to all electrical rooms
Vertical:
- Use 10ft Riser in Typical
- GA or HD - 1" conduit / HR - (2) 2" conduits)
Annunciator Panels
- Fire Alarm Annunciator (FAA),
- Fire Alarm Annunciator Panel (FAAP)
ANNUNCIATORS (CA.30.27.2/3)
Remote Serial Annunciator, LCD Display - PVC
- Measure from the Fire Command Room to FAA or Lobby
Sleeving
Devices
- Takeoff floor plans in order
- Takeoff enlarged drawings
Smoke Detectors
Design Build: Count every stairwell at every level.
Pull Stations
Design Build: Count every stairwell at every level and every exterior exit.
Flow-Tamper Switches
No free air. if wood frame, take off as EMT.
Design Build: Count every stairwell at every level.
Magnetic Door Holders
Mech Connection - PVC AL Flex - 20 A
Design Build: Count every set of double doors. (Typical of elevator lobbies and corridors)
Speaker Strobes
Design Build:
- Count every 75 ft,
- measure with circles on Bluebeam
- or divide relevant SF area by 4415
\pi(\frac{75}{2})^2 \approx 4415
- every elevator lobby,
- and every BOH room on the first floor and garage levels.
Fire Smoke Dampers (FSD's)
Take off both FA and Electrical
- Misc Assemblies
3. Extension (Review and Checking)
- Sleeving