# Article 110 Requirements for Electrical Installations
|
|
|
|
## Part I. General
|
|
|
|
### 110.1 Scope.
|
|
|
|
This article covers general requirements
|
|
for the examination and approval, installation and use,
|
|
access to and spaces about electrical conductors and equipment;
|
|
enclosures intended for personnel entry;
|
|
and tunnel installations.
|
|
|
|
> [!info] Informational Note:
|
|
> See Informative Annex J for information regarding ADA accessibility design.
|
|
|
|
<!-- TODO: TEXT OMITTED -->
|
|
|
|
### 110.14 Electrical Connections.
|
|
|
|
Because of different characteristics of dissimilar metals,
|
|
devices such as pressure terminal
|
|
or pressure splicing connectors and soldering lugs
|
|
shall be identified for the material of the conductor
|
|
and shall be properly installed and used.
|
|
Conductors of dissimilar metals
|
|
shall not be intermixed in a terminal or splicing connector
|
|
where physical contact occurs between dissimilar conductors
|
|
(such as copper and aluminum or aluminum and copper-clad aluminum),
|
|
unless the device is identified for the purpose and conditions of use.
|
|
Materials such as solder, fluxes, inhibitors, and compounds,
|
|
where employed, shall be suitable for the use
|
|
and shall be of a type that will not adversely affect
|
|
the conductors, installation, or equipment.
|
|
Connectors and terminals for conductors more finely stranded
|
|
than Class B and Class C stranding as shown in Chapter 9, Table 10,
|
|
shall be identified for the specific conductor class or classes.
|
|
|
|
#### 110.14(C) Temperature Limitations.
|
|
|
|
The temperature rating associated with the ampacity of a conductor
|
|
shall be selected and coordinated so as not to exceed the lowest
|
|
temperature rating of any connected termination, conductor, or device.
|
|
Conductors with temperature ratings higher than specified for
|
|
terminations shall be permitted to be used
|
|
for ampacity adjustment, correction, or both.
|
|
|
|
##### 110.14(C)(1) Equipment Provisions.
|
|
|
|
The determination of termination provisions of equipment
|
|
shall be based on 110.14(C)(1)(a) or (C)(1)(b).
|
|
Unless the equipment is listed and marked otherwise,
|
|
conductor ampacities used in determining equipment termination provisions
|
|
shall be based on Table 310.16 as appropriately modified by 310.12.
|
|
|
|
* (a) Termination provisions of equipment for circuits rated 100 amperes or less,
|
|
or marked for 14 AWG through 1 AWG conductors,
|
|
shall be used only for one of the following:
|
|
* (1) Conductors rated 60°C (140°F).
|
|
* (2) Conductors with higher temperature ratings,
|
|
provided the ampacity of such conductors
|
|
is determined based on the 60°C (140°F) ampacity of the conductor size used.
|
|
* (3) Conductors with higher temperature ratings
|
|
if the equipment is listed and identified for use with such conductors.
|
|
* (4) For motors marked with design letters B, C, or D,
|
|
conductors having an insulation rating of 75°C (167°F) or higher
|
|
shall be permitted to be used,
|
|
provided the ampacity of such conductors
|
|
does not exceed the 75°C (167°F) ampacity.
|
|
|
|
* (b) Termination provisions of equipment
|
|
for circuits rated over 100 amperes,
|
|
or marked for conductors larger than 1 AWG,
|
|
shall be used only for one of the following:
|
|
* (1) Conductors rated 75°C (167°F)
|
|
* (2) Conductors with higher temperature ratings,
|
|
provided the ampacity of such conductors
|
|
does not exceed the 75°C (167°F) ampacity of the conductor size used,
|
|
or up to their ampacity if the equipment is listed and identified
|
|
for use with such conductors
|
|
|
|
##### 110.14(C)(2) Separate Connector Provisions.
|
|
|
|
Separately installed pressure connectors shall be used with conductors at the ampacities not exceeding the ampacity at the listed and identified temperature rating of the connector.
|
|
|
|
Informational Note:
|
|
With respect to 110.14(C)(1) and (C)(2),
|
|
equipment markings or listing information may additionally restrict
|
|
the sizing and temperature ratings of connected conductors.
|
|
|
|
#### 110.14(D) Terminal Connection Torque.
|
|
|
|
Tightening torque values for terminal connections
|
|
shall be as indicated on equipment
|
|
or in installation instructions provided by the manufacturer.
|
|
An approved means shall be used to achieve the indicated torque value.
|
|
|
|
Informational Note No. 1:
|
|
Examples of approved means of achieving the indicated torque values
|
|
include torque tools or devices such as shear bolts
|
|
or breakaway-style devices with visual indicators
|
|
that demonstrate that the proper torque has been applied.
|
|
|
|
Informational Note No. 2:
|
|
The equipment manufacturer can be contacted
|
|
if numeric torque values are not indicated on the equipment
|
|
or if the installation instructions are not available.
|
|
Informative Annex I of UL Standard 486A-486B, Standard for Safety-Wire Connectors,
|
|
provides torque values in the absence of manufacturer's recommendations.
|
|
|
|
Informational Note No. 3:
|
|
Additional information for torquing threaded connections and terminations
|
|
can be found in Section 8.11 of NFPA 70B-2019, Recommended Practice for Electrical Equipment Maintenance.
|