title: Fire Resistive Wiring Methods
|
|
---
|
|
# Fire Resistive Wiring Methods
|
|
|
|
## Requirements
|
|
|
|
Permitted methods for fire protection of emergency feeders
|
|
are specified in 700.10(D)(1).
|
|
|
|
![[nfpa-70_700_emergency-systems#700.10(D)(2) Feeder-Circuit Wiring.]]
|
|
|
|
the requirements of which only apply to occupancies listed in 700.10(D)(1)
|
|
|
|
![[nfpa-70_700_emergency-systems#700.10(D)(1) Occupancies.]]
|
|
|
|
Note that even in these occupancies only [[nfpa-70_100_definitions#Feeder.|feeders]]
|
|
require fire protection, not [[nfpa-70_100_definitions#Branch Circuit.|branch circuits]].
|
|
|
|
## Construction
|
|
|
|
> [!info] Keywords
|
|
> * Low Smoke Zero Halogen (LSZH)
|
|
|
|
|
|
* Mineral Insulated (MI) Cable
|
|
* Fire Resistive Metal-Clad (MC) Cable
|
|
* Fire Resistive Cable-in-Conduit (CIC)
|
|
|
|
> [!info] "Vitalink" vs "Lifeline" cable
|
|
> VITALink® and Lifeline® are brand names
|
|
> (of Omni Cable and Prysmian Group respectively),
|
|
> not cable types.
|
|
> *Both* brands include MC *and* CIC cables.
|