id:
|
||||
aliases: []
|
||||
title: Hilltop Gardens
|
||||
tags: []
|
||||
up: "[[conest-projects]]"
|
||||
---
|
||||
# Hilltop Gardens
|
||||
|
||||
6 buildings + clubhouse
|
||||
3 building types
|
||||
|
||||
## ConEst Questions
|
||||
|
||||
### Area Breakdowns
|
||||
|
||||
Since residential building types have corridors
|
||||
it will be necessary to create Areas for each level.
|
||||
|
||||
## Bid Questions
|
||||
|
||||
### Voltage Drop
|
||||
|
||||
VOLTAGE DROP CALCULATIONS ON ALL FEEDERS AND BRANCH CIRCUITS
|
||||
HAVE BEEN PERFORMED IN ACCORDANCE WITH THE STATE OF FLORIDA 2023 FBC ENERGY CONSERVATION C405.5.3.
|
||||
THE CONTRACTOR IS RESPONSIBLE TO BE FAMILIAR WITH THE 2020 FBC ENERGY CONSERVATION
|
||||
AND SHALL UPSIZE THE CONDUCTORS FOR FEEDER AND BRANCH CIRCUITS
|
||||
BASED ON THE ACTUAL ROUTING IN THE FIELD.
|
||||
|
||||
### Floor Boxes
|
||||
|
||||
> [!cite] E.0.X.1 - "ELECTRICAL NOTES" Note 25
|
||||
> RECEPTACLES WHICH ARE SHOWN WALL MOUNTED ON THE ELECTRICAL DRAWINGS
|
||||
> ON WALLS WHICH, ON THE ARCHITECTURAL DRAWINGS AND ELEVATIONS
|
||||
> ARE SHOWN AS GLASS OR PARTITIONS,
|
||||
> SHALL BE FLUSH FLOOR DUPLEX RECEPTACLES
|
||||
> MOUNTED ADJACENT TO BASE OR WALLS.
|
||||
|
||||
**C405.10 Voltage drop.**
|
||||
The total voltage drop across the combination of customer-owned service conductors,
|
||||
feeder conductors and branch circuit conductors
|
||||
shall not exceed 5 percent.
|
||||
|
||||
### Wiring Method Selection
|
||||
|
||||
[[wiring-method-selection]]
|
||||
|
||||
> [!cite] E.0.X.1 - "ELECTRICAL NOTES" Note 32
|
||||
> ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC RACEWAYS.
|
||||
> RACEWAYS IN SLAB-ON-GRADE OR BELOW GRADE SHALL BE SCHEDULE 40 PVC.
|
||||
> TRANSITIONS FROM BELOW TO ABOVE GRADE
|
||||
> SHALL BE WITH RIGID STEEL ELBOWS WITH P.V.C. JACKET
|
||||
> OR APPROVED EQUIVALENT PROTECTION.
|
||||
> MET FITTINGS SHALL BE MALLEABLE IRON OR STEEL.
|
||||
> CONNECTORS SHALL BE INSULATED THROAT TYPE.
|
||||
|
||||
#### Cable Uses
|
||||
|
||||
> [!cite] E.0.X.1 - "ELECTRICAL NOTES" Note 32
|
||||
> ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC RACEWAYS.
|
||||
|
||||
> [!cite] E.0.X.1 - "ELECTRICAL NOTES" Note 27
|
||||
> STEEL TYPE "MC" CABLE #12 AWG AND #10 AWG
|
||||
> WITH A FULL-SIZED GROUNDING CONDUCTOR
|
||||
> MAY BE USED WHERE PERMITTED
|
||||
> BY BOTH THE N.E.C. AND LOCAL ORDINANCE,
|
||||
> IN THE FOLLOWING APPLICATIONS:
|
||||
> * A. IN WALLS FOR HORIZONTAL DEVICE CONNECTION ONLY.
|
||||
> HOMERUNS TO PANELBOARDS SHALL BE EMT OR PVC (BELOW GRADE).
|
||||
|
||||
#### Rigid Elbows
|
||||
|
||||
Rigid elbows are required,
|
||||
but neither proposal mentions them.
|
||||
|
||||
> [!cite] E.0.X.1 - "ELECTRICAL NOTES" Note 32
|
||||
> TRANSITIONS FROM BELOW TO ABOVE GRADE
|
||||
> SHALL BE WITH RIGID STEEL ELBOWS WITH P.V.C. JACKET
|
||||
> OR APPROVED EQUIVALENT PROTECTION.
|
||||
|
||||
#### Fire Alarm Wiring Methods
|
||||
|
||||
|
||||
|
||||
### Differences in Scope Between Customers
|
||||
|
||||
2 Customers
|
||||
KAST Construction
|
||||
Hedrick Brothers Construction
|
||||
Different scope
|
||||
|
||||
DAS Conduit in separate bid item
|
||||
|
||||
#### Awarded to Hedrick Brothers?
|
||||
|
||||
BPM
|
||||
2026-03-23 Nicole Bisbee:
|
||||
Per correspondence from KAST
|
||||
“Please note that KAST has **not** been awarded this project.
|
||||
It appears the project will be undertaken by Hedrick Brothers.”
|
||||
|
||||
Most recent proposal to KAST is 2026-02-26.
|
||||
Assuming this one can be ignored.
|
||||
|
||||
### AIC Ratings
|
||||
|
||||
> [!quote] E.4.X.1 "RISER NOTES" (B)
|
||||
> ALL BREAKERS SHALL BE SERIES RATED AT 22K TO THE MAIN BREAKER.
|
||||
> MAIN BREAKER AIC RATING IS 65K.
|
||||
> UNIT APARTMENT PANELBOARD MAIN BREAKER AIC RATING 10K.
|
||||
> SEE ATTACHED DETAIL ON SHEET E-6.4 FOR FURTHER DETAILS.
|
||||
|
||||
### Lighting Inverters
|
||||
|
||||
> E.2.1.1 "KEY NOTES" 2
|
||||
> LIGHTING CIRCUIT TO BE ROUTED THROUGH INVERTER.
|
||||